14
IM620-1
Installation
Panel Location and Mounting
The MAG panel is suitable for indoor use only. Table 8 lists the allowable temperature and humidity
ranges. Locate the panel at a convenient height, and allow adequate clearance for the door swing.
Mount the panel to the wall with screws or bolts. Four ¼-inch openings are provided at the corners of
the panel. The panel weighs approximately 60 lb. (27 kg). Figure 6 shows the panel dimensions.
The MAG Panel is equipped with special door hinges that have a friction adjustment screw. By
adjusting this screw you can prevent the panel door from swinging open or closed unexpectedly.
Table 8. MAG Panel Environmental Specifications
Panel State
Temperature
Relative Humidity
Operating
30 – 100°F (–1 – 38°C)
10 – 95% (noncondensing)
In storage
0 – 125°F (–18 – 52°C)
10 – 95% (noncondensing)
Figure 6. MAG Panel Dimensions
6-3/8"
15-3/8"
Bottom View
24"
Front View
Left Side View
1/4" (6.4) Dia. mounting slots (2)
Hinge friction adjustment screw
7/8" (22.3) Dia.
knockouts
24"
16"
22"
4"
4"
1-7/8"
1-7/8"
4-3/4"
Right Side View
7/8" (22.3) Dia. knockouts
1-3/4"
21"
15"
12"
9"
6"
3"
10-7/8"
22-1/8"
18"
(102)
(406)
(102)
(610)
(48)
(162)
(276.2)
(391)
(562)
(48)
(610)
(559)
(44.5)
(121)
(76)
(152)
(229)
(305)
(381)
(457)
(533)
Numbers in parenthesis = millimeters (mm)
1/4" (6.4) Dia. mounting slots (2)
a0107