Alarm Table
Display
Type
Comp.
pump
fan
Resist.
valve
alarm
H1
high pressure
OFF
-
ON
-
-
ON
L1
low pressure
OFF
-
OFF
-
-
ON
t1
overload
OFF
OFF
OFF
-
-
ON
FL
flow detector
OFF
OFF
OFF
-
-
ON
E1, E2, E3
probe
OFF
OFF
OFF
-
-
ON
n1
automatic timer
-
-
-
-
-
-
EE
eeprom run
-
-
-
-
-
-
EL
zero crossing
-
-
-
-
-
ON
d1
defrosting ON
-
-
-
-
-
-
r1
defrosting error
-
-
-
-
-
-
A1
antifreeze
OFF
OFF
-
-
ON
LO
low ambient temperature
-
-
-
-
-
ON
EU
low supply voltage
-
-
-
-
-
-
EO
high supply voltage
OFF
OFF
OFF
OFF
OFF
OFF
EP
eeprom boot
OFF
OFF
OFF
OFF
OFF
OFF
Cn
discon. Remote terminal
-
-
-
-
-
-
Ht
high temperature
-
-
-
-
-
ON
Electrical features
Buttons and Relative Messages on Display
Power supply
Voltage supply range
24V –15%…+10% 50/60Hz (20,4V~26,4Vac)
Maximum power absorbed by the device
3W
Characteristics of the fuse (obligatory) to be inserted
in series to the unit power supply
315mAT
Power driving
Max. current for each power connector
2A
Relay output current (each relay, resistive load)
2A 250 V~
Relay output current (maximum 1 relay, resistive load)
3A 250 V~
Switching maximum number (each relay)
7000
Switching maximum time (each relay)
10 s
Setting and displaying the set point and the main control parameters (DIRECT
parameters).
The DIRECT parameters are set-points (Cooling and Heating) and main control parameters of the unit
(Cooling and Heating differentials, water temperature, condensation temperature/pressure). If
you press SEL for more than 5 seconds the display shows the code of the first parameter – the Cooling
set-point- that can be modified. Pressing the
Ÿ
and
ź
buttons allows to scroll all direct
parameters. Press SEL again to display the required DIRECT parameter and modify its value (with the
Ÿ
and
ź
buttons). Press PRG to store the modified parameters and exit the procedure, while the
SEL button allows to return to the DIRECT parameters menu. On setting the parameters, the
display will automatically flash after a few seconds if no buttons are pressed. If you do not press any
button within 60 seconds after having entered this procedure, the unit will return to normal operation
without storing the values of the modified parameters.
Setting and displaying USER parameters
These “working” parameters are protected by a password (22) to prevent any unauthorized access to
the data. Press PRG for more than 5 seconds (the buzzer must be off) to enter the USER
parameters (the unit “operating” parameters) menu and buttons
Ÿ
and
ź
to select the password
value, or, if the password is correct (22), press SEL to enter the USER parameter section. On
setting the password, the display will automatically flash after a few seconds if no buttons are
pressed. USER parameters selection: the display
6
Summary of Contents for M4AC040A
Page 33: ...Outlines and Dimensions Model MAC040 050 058A AR M4AC040 050 058A AR Bottom Compartment 32...
Page 34: ...Model MAC075 100 125B BR 33...
Page 35: ...Top Compartment Bottom Compartment 34...
Page 54: ...Refrigerant Circuit Diagram Model M4AC075BRE 100BRE 125BRE 53...
Page 59: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...