Air Cooled Chiller
MODEL
M4AC040ARE
M4AC050ARE
M4AC058ARE
Btu/hr
30000/33000
40000/43000
48000/50000
kcal/hr
7560/8316
10080/10836
12100/12600
Watt
8792/9669
11723/12600
12068/14650
MATERIAL
FINISH
THICKNESS
mm
TOTAL
HEIGHT (H)
mm (in)
UNIT
WIDTH (W)
mm (in)
DIMENSION
DEPTH (D)
mm (in)
TOTAL WEIGHT
kg
150
155
160
NOISE LEVEL
dB-A
58
58
71
EVAPORATOR
TYPE
PLATE MATERIAL
WATER VOLUME
m
3
0.00075
0.001
0.0014
NOMINAL WATER FLOW
l/s
0.42
0.56
0.70
BPHE PRESSURE DROP VS NOMINAL FLOW RATE
kPa
41.00
37.20
37.10
UNIT PRESSURE DROP VS NOMINAL FLOW RATE
kPa
42.11
39.32
39.80
WATER LINE (HYDRAULIC KIT)
TYPE
POWER SUPPLY
V/Ph/Hz
RUNNING CURRENT
Amp
1.02
1.02
1.05
WATER FLOW RATE
GPM (l/s)
6.78 (0.427)
8.89 (0.561)
11.10 (0.700)
INSTALLATION PIPE CONNECTION
mm (in)
HEAD
m
24
22
20
MATERIAL
CAPACITY/ VOLUME
litres
CONDENSER COIL
TYPE
MATERIAL
WALL THICKNESS
mm (in)
OUTER DIAMETER
mm (in)
MATERIAL
THICKNESS
mm (in)
ROWS
2
2
2
FIN PER INCH
14
16
16
FACE AREA
m
2
( ft
2
)
CONDENSER FAN
TYPE/DRIVE
QUANTITY
BLADE MATERIAL
BLADE DIAMETER
mm (in)
POWER SUPPLY
V/Ph/Hz
RATED RUNNING CURRENT
Amp
1.09
1.09
2.8
RATED INPUT
Watt
241
241
655
RATED OUTPUT
Watt
145
145
400
MOTOR POLES
8
8
6
AIR VOLUME
L/s / cfm
2124 / 4500
COMPRESSOR
TYPE
POWER SUPPLY
V/Ph/Hz
RATED RUNNING CURRENT
Amp
5.85
8.42
8.12
RATED INPUT
Watt
3,180
4,310
4,740
MAXIMUM STARTING CURRENT
Amp
49.3
65.5
74
PROTECTION DEVICES
STAGE OF CAPACITY CONTROL
REFRIGERANT
TYPE
CONTROL
CHARGING MASS
kg
2.35
2.55
2.60
NOMINAL CAPACITY (COOLING/HEATING)
CASING
Electro-galvanised Mild Steel
Polyester Powder
1
1,342 (52.8)
1,032 (40.6)
558 (22.0)
Brazed Plate Heat Exchanger
Stainless Steel
PUMP
Horizontal Multistage End-Suction
380 - 420 / 3 / 50
PIPING
42mmBSP (1 1/4")
TANK
Black Mild Steel
32
Cross Finned Tubes
TUBE
Seamless Copper
0.35 (0.014)
9.52 (3/8)
FIN
Aluminium
0.127 (0.0005)
0.87 (9.36)
Propeller/Direct
1
Acryl Styrene Resin
609.6 (24)
220 - 240 / 1 / 50
1652 / 3500
Scroll
380 - 420 / 3 / 50
Overload Protection, Differential Pressure and H/L Pressure Switch
On/Off
R407C
Thermostatic Expansion Valve
Notes :
1) All specifications are subjected to change by manufacturer without prior notice.
2) Nominal values are based on entering / leaving chilled water temperature 12°C / 7°C and air ambient temperature 35°C.
3) Nominal values are based on entering / leaving chilled water temperature 40°C / 45°C and air ambient temperature 7°C.
17
Summary of Contents for M4AC040A
Page 33: ...Outlines and Dimensions Model MAC040 050 058A AR M4AC040 050 058A AR Bottom Compartment 32...
Page 34: ...Model MAC075 100 125B BR 33...
Page 35: ...Top Compartment Bottom Compartment 34...
Page 54: ...Refrigerant Circuit Diagram Model M4AC075BRE 100BRE 125BRE 53...
Page 59: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...