Troubleshooting with Microprocessor
(Not Include Carel Controller)
Symptoms
Possible Causes
Remedial Action
1. PCB display ‘CO’
x
Compressor thermal relay tripped
x
Terminal
loose
x
Reset the thermal relay and carefully
monitor unit operation when it is
restarted
x
Tighten terminal screws.
2. PCB display ‘PO’
x
Pump thermal relay tripped
x
Terminal
loose
x
Reset the thermal relay and carefully
monitor unit operation when it is
restarted.
x
Tighten terminal screws
3. PCB display ‘FL’
x
Flow switch connection loose
x
Water volume too low
x
Wrong direction of water flow
x
Tighten terminal screws
x
Add water into the system
x
Interchange power input phase
4. PCB, display ‘HP’
x
Discharge pressure too high
x
Overcharge
x
Coil
dirty
x
Condenser fan does not work
x
Expansion valve stuck in open
position
x
Reset the pressure switch and
observe the unit operation when it is
restarted
x
Contact local dealer
x
Clean the coil with chemical
detergent
x
Contact local dealer
x
Replace it
5. PCB display ‘LP’
x
Suction pressure too low
x
Undercharge
x
Gas
leak
x
Water flow rate too low
x
Reset the pressure switch and
observe the unit operation when it is
restarting.
x
Contact local dealer
x
Contact local dealer
x
Adjusting the flow rate
6. PCB display ‘E3’
x
Antifreeze protection activated.
x
Water flow rate too low
x
Bubble in the heat exchanger
x
Check the temperature setting
x
Adjusting the flow rate
x
Increase the water volume
48
Summary of Contents for M4AC040A
Page 33: ...Outlines and Dimensions Model MAC040 050 058A AR M4AC040 050 058A AR Bottom Compartment 32...
Page 34: ...Model MAC075 100 125B BR 33...
Page 35: ...Top Compartment Bottom Compartment 34...
Page 54: ...Refrigerant Circuit Diagram Model M4AC075BRE 100BRE 125BRE 53...
Page 59: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...