background image

9.  Too much cooling.

10.   “Sweating.”

11.   Blowers won’t operate on Heat.

12.   Equipment is noisy.

13.   Insufficient or no heat.

a.   Thermostat set too low. 

b.   Defective thermostat

a.   Condensate drain from evaporator to condenser 

plugged. 

b.   Insulating seals on equipment damaged. 

c.   Evaporator blower motor not up to speed. 

d.   Evaporator blower incorrectly positioned.

a.   No power.

b.   Heat is off (equipment with heat fan lock out).

c.   Faulty push-button switch.

d.   Loose connections at push-button switch.

e.   Thermostat set too low.

a.   Blower rubbing against enclosure.

b.   Blower motor bearings dry.

c.  Loose blower hold-down nuts on motor-bracket

 

assembly

d.   Refrigerant absorbed in compressor oil after extended

 

shutdown.

e.   Equipment improperly installed.

f.   Damper solenoid hums.

g.   Loose terminal box cover on side of compressor.

h.   Loose electrical components.

i.   Copper tubing vibrating.

j.   Harmonics.

a.   No steam or hot water being applied. 

b.   No power.

c.   Faulty push-button switch. 

d.   Loose connection at push-button switch. 

e.   Thermostat set too high. 

f. 

Thermostat faulty. 

g.   No power output on transformer secondary. 

h.   Inoperative valve.

 

1) Steam valve N/C.

 

2) Hot water valve N/C.

a.   Adjust.

b.   Replace.

a.   Remove obstructions to water flow.

b.   Adjust or replace.

c.   Check for correct voltage. Replace motor if necessary.

d.   Tighten.

a.   See No. 1.

b.   Open heat valve or turn on heating system.

c.   Replace.

d.   Tighten.

e.   Adjust. Rotate control knob to “warmer”.

a.   Adjust fan position on motor shaft or reposition fan 

motor bracket assembly.

b.   Replace motor.

c.   Align blower assembly and tighten nuts.

d.   Noise will disappear after equipment runs awhile.

e.   Make necessary adjustments to components.

f.   Check for proper adjustment. Apply silicone oil or 

grease to gap between solenoid and armature.

g.   Tighten.

h.   Fasten securely.

i.   Occasionally equipment will have noise for no ap-

parent reason. Inspection has revealed no loose 

components that might be the source of the noise. 

Due to the action of the compressor, it is possible to 

have internal noise develop if the refrigerant tubing has 

become bent even slightly. To distinguish this condition 

from the simple rattle producing vibration caused by 

loose screws, nuts and other components, grasp the 

refrigerant tubing at various points throughout the sys

-

tem until a point is found where the noise is eliminated 

or reduced. Bend the copper

 

tubing very gently until the noise disappears.

j. 

Tighten.

a.   Contact building management.

b.   Check power supply line fuse, circuit breakers. Blown 

fuses would indicate circuit overloading, a short circuit, 

or a grounded condition in the circuit.

c.   Replace.

d.   Replace wire or tighten.

e.   Adjust. Rotate knob to “warm.”

f. 

Replace.

g.   Replace.

h.

 

1) Temporarily lock valve open; replace.

 

2) Replace.

Troubleshooting

These items should be checked by a qualified service technician only.

 

Trouble 

Cause 

Cure

Notes:

This guide was prepared with standard equipment in mind. If equipment is special, it may not be entirely applicable.

*  If equipment is still in warranty.

** 

Note:

 Before trying to correct the noise, determine its cause such as conditioned air blower, compressor or condenser blower. Operate the  

 

conditioned air blowers only. If this doesn’t cause the noise, operate on cooling. Then disconnect one compressor lead. If the noise stops, the  

 

compressor is the source, If not, it is caused by the condenser blower.

©2008 McQuay International   •   www.mcquay.com  •  800-432-1342 

IM 882 / Page 36 of 36 (Rev 1-08)

 

®

This document contains the most current product information as of this printing. For the most up-to-date 

product information, please go to 

www.mcquay.com.

 

Summary of Contents for IM 938-1

Page 1: ...Installation Maintenance Data Group PTAC Part No 668109501 Date January 2008 IM 882 2008 McQuay International Applied Packaged Terminal Air Conditioner 16 x 42 PDAC PDHP With Top Mounted Hydronic Heat...

Page 2: ...at Section 13 Installation of Room Cabinet 14 Supply and Return Coil Arrangements 14 Controls PDAC PDHP Digital Touchpad Control 15 19 Inputs Outputs 15 Keys and Indicators Labels 15 Display Function...

Page 3: ...be damaged in transit due to rough handling even though the carton may not show external damages When the damage is discovered upon unpacking make a written request for inspection by the carrier s ag...

Page 4: ...lectric Heat H Hydronic A Hydronic w Intermediate Electric Y None PDHP only Electric Heat A 2 5 Kw B 3 5 Kw C 5 0 Kw Y None Hydronic Heat Type S Steam Top Mount Normally Closed T Steam Subbase Normall...

Page 5: ...ew or existing buildings The Figure 1 Exploded View of the 16 x 42 PDAC PDHP with Top Mounted Hydronic Unit self contained refrigerant system delivers cooling to the desired space Heating can be accom...

Page 6: ...4 273 143 4 375 133 4 143 4 349 375 103 4 273 153 4 400 143 4 153 4 375 400 103 4 273 163 4 425 153 4 163 4 400 425 103 4 273 173 4 451 163 4 173 4 425 451 Note Electrical rough in should be located b...

Page 7: ...it may cause leaks If the louver frame is to be installed in a panel wall it should be installed at the same time as the wall sleeve WARNING Residential and institutional cleaning compounds can cause...

Page 8: ...propriatefasteners Useholesprovided seeFigure15 page 12 or drill additional holes as required to secure firmly CAUTION Do not drill holes in the base of the wall sleeve Use shims between the wall and...

Page 9: ...eat Coil Section 3 1 2 Thick Batt Insulation 1 5 8 Metal Stud 16 O C Window Stool Insulation Wet Panel 16 11 4 42 Outdoor Side of Sleeve X 63 8 Optional Leveling Leg 13 3 4 X D Figure 11 16 x 42 wall...

Page 10: ...of all debris that may interfere with installation Figure 12 Wall sleeve installation using top angles and field supplied continuous louver 133 4 349mm 11 4 38mm Insulated Panel Optional Top Angle 16...

Page 11: ...heat section and room cabinet The wall sleeve should also be recessed enough to accom modate the outside louver Level wall sleeve side to side and pitch to outside 1 8 ft to assure proper sleeve drai...

Page 12: ...g the wall sleeve in the opening is accomplished asshowninFigure15 Itisrecommendedthatrubberisola tion washers be used with the fasteners to minimize sound transmission from the equipment to the wall...

Page 13: ...uto mode it will cycle the indoor fan when there is a call for heating or cooling See page 28 for jumper placement details 15 Set the temperature limiting feature to the desired range of thermostat op...

Page 14: ...omplete so as not to damage the room cabinet after it has been installed Attaching the room cabinet can be com pleted as follows 1 Firmly grasp the room cabinet and lift it over the heat section There...

Page 15: ...tton Remote must be aimed in a line of sight of the window in upper right corner on the front panel at less than a 45o angle from center of the window The control board will beep when any button is pr...

Page 16: ...compressor and condenser fan shall turn on when Y signal is high 3 Cold start feature see Modes of Operation Cold Start Cool dry mode see Cold Dry Mode and Sleep feature see Sleep Feature are not avai...

Page 17: ...higher than the set point It will stop if the space temperature sensor is 2 F or lower than the set point subject to timing requirements In the Cool Mode the indoor fan will operate according to the...

Page 18: ...room temperature and the set point is less than 2 F This will also occur after a Cold Start or a Mode change from Cool to Cool Dry During this time the fan will operate in the Mode and Speed selected...

Page 19: ...ll not operate In single motor units the outdoor fan will run along with the indoor fan Control Board Configuration To enter the Configuration Mode simultaneously press the Up and Down buttons for 5 s...

Page 20: ...reaches 30 F and stays there for at least five 5 minutes 3 The compressor has run for at least 90 seconds Sleep Timer is overridden during this operation Anti freeze Protection is active in all modes...

Page 21: ...Found _ __________________________________________________________________ _______________________________________________________________________________________ _____________________________________...

Page 22: ...s equipment After the equipment leaves the factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected accidentally or fan motors move on their ba...

Page 23: ...mode However the control pad LED display will indicate the mode of operation and the room temperature Controls Premium Programmable Digital Touchpad Control Operating Instructions LED with Program Set...

Page 24: ...by pressing Mode button 2 1 Once in the configuration mode the default temperature scale will be displayed as shown below Toggle the temperature scale to degree Celsius by pressing either or button 2...

Page 25: ...thermostat for each period of the day repeat steps 3 3 through 3 7 Further the thermostat can be programmed for each individual day of the week or use the SimplesetTM feature as described below 3 9 S...

Page 26: ...le stage heat single stage cool or single stage electric heat pump Terminations RC RH C W Y O B G Controls Remote Wall Mounted Thermostats Wall mounted thermostats are available for the Applied PTAC u...

Page 27: ...urns off Vacation hold overrides programming Lockout feature prevents unwanted tampering Clear backlit display makes it easy to see time temperature and setpoint even in the dark No batteries required...

Page 28: ...emote mounted thermostats should be wired as shown in Figure 30 Other considerations for this arrangement are as follows 1 When wiring the low voltage plug and receptacle disconnect provide enough wir...

Page 29: ...y the room temperature 3 Jumper Placement to Select Controller Type A Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across SEC Secondary to select Control...

Page 30: ...otor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Re...

Page 31: ...ssor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface...

Page 32: ...removal system and assure proper operation Pour at least two 2 cups of water into evaporator drain pan and verify proper operation Clean condensate drain and clear weep holes located at the bottom re...

Page 33: ...ion of the rest of the system A further advantage is that a failed part can be quickly and easily replaced thus minimizing the inoperative time of the equipment This is so however only if a replacemen...

Page 34: ...rees below minimum setpoint limit LA Low Ambient Lockout Outdoor air temperature is below 35 F Fault and Protection Codes for Applied PTAC PTHP Control Board Fault code Description Cause for the fault...

Page 35: ...tructed discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e...

Page 36: ...e oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Occasionally equipment will have noise for no ap parent reason Inspection has revealed no loose components that might...

Reviews: