1-6
Ø Tube, D
A (mm)
Inch
mm
Imperial
Rigid
1/4"
6.35
1.3
0.7
3/8"
9.52
1.6
1.0
1/2"
12.70
1.9
1.3
5/8"
15.88
2.2
1.7
3/4"
19.05
2.5
2.0
Spanar
Torque Wrench
Indoor Piping
Flare Nut
Flared Tube
Flare Joint
Pipe Size (mm/in)
Torque (Nm)
6.35 (1/4)
18
9.53 (3/8)
42
12.7 (1/2)
55
15.88 (5/8)
65
19.05 (3/4)
78
ELECTRICAL WIRING CONNECTION
Electrical Wiring Connection For CE Series 10~25C
Indoor Unit
CE 30C
CE 35C
Outdoor Unit
SL 30C
SL 35C
Voltage range (2)
220V – 240V/1Ph/50Hz +
!
or 208V - 230V/1Ph/60Hz+
!
Recommended fuse (1)
A
25
25
Power Supply Cable size
mm
2
4.0
4.0
Number of conductors (1)
3
3
Interconnection Cable size
mm
2
4.0
4.0
Number of conductors (1)
4
4
Electrical Wiring Connection For CE Series 30~35C
The electrical power must be provided with
protection devices (circuit breaker or fuse)
with double pole separation system (phase +
neutral) with minimum contact gap of 3mm.
!
Terminal Strip
Indoor Unit
Interconnection Cable
Terminal Strip
Outdoor Unit
COMP
L
N
COMP
N
Indoor Unit
CE 10C
CE 15C
CE 18C
CE 20C
CE 25C
Outdoor Unit
SL 10B
SL 15B
SL 18B
SL 20B
SL 25B
Voltage range (2)
220V – 240V/1Ph/50Hz +
!
or 208V - 230V/1Ph/60Hz+
!
Recommended fuse (1)
A
10
10
16
16
20
Power Supply Cable size
mm
2
1.5
1.5
2.5
2.5
2.5
Number of conductors (1)
3
3
3
3
3
Interconnection Cable size
mm
2
1.5
1.5
2.5
2.5
2.5
Number of conductors (1)
3
3
3
3
3
CE 10~25C
Power Supply
Cable
IMPORTANT:
(1) These values are for information only, they should be checked and selected to comply with the local and/
or national codes and regulations. They are also subjected to the type of installation and size of conductors
used.
(2) The appropriate voltage range should be checked with label data on the unit. ETL listed unit is only
applicable to 60Hz power supply only.