As the OAT increases above the Outdoor Air Low Limit (OALL), the Actual Leaving Water Setpoint
is decreased from its Leaving High Limit (Leaving Water Setpoint plus Leaving Reset Band) to the
Leaving Water Setpoint. When OAT reaches the OAHL, the Actual Leaving Water Setpoint equals
the Leaving Water Setpoint (AI4). If the OAT sensor is missing or unreliable, no reset occurs and the
Actual Leaving Water Setpoint equals the Leaving Water Setpoint. If the Leaving Water Sensor (AI1)
becomes unreliable, the compressor command is forced to 0%.
Return Water Reset (optional Return Water Sensor is required)
When selected, a Return Water Temperature (RWT) sensor is connected to TB-7 terminals #134 and
#135. Four variables are used to setup the reset ramp that calculates the Actual Leaving Water
Setpoint. These are: Leaving Water Setpoint (AI-4), Reset Band selected with a Zone Terminal,
Return Water High Limit (RWHL), and Return Water Reset Band (RWRB).
Figure 20, Return Water Reset
LWRB
LWSP
RWLL
RWHL
RWRB
(RWLL=RWHL - RWRB)
As the RWT increases above the Return Water Low Limit (RWLL), the controller decreases the
Actual Leaving Water Setpoint from its Leaving High Limit (Leaving Water Setpoint plus Leaving
Reset Band) to the Leaving Water Setpoint. When RWT reaches the RWHL, the Actual Leaving
Water Setpoint equals the Leaving Water Setpoint (AI-4). If the RWT sensor is missing or unreliable,
no reset occurs and the Actual Leaving Water Setpoint equals the Leaving Water Setpoint. If the
Leaving Water Sensor (AI-1) becomes unreliable, the compressor command is forced to 0%.
When Return Water Reset is chosen, a Fail Smart Logic option is also available. This option works as
follows. If the Leaving Water Sensor (AI-1) becomes unreliable, the controller switches from
Leaving Water control to Return Water control. Actual Return Water Setpoint equals Leaving Water
Setpoint (AI-4) plus an adjustable Leaving Water Setpoint Offset. This value takes into account the
temperature differential between Leaving and Return water temperatures, which is typically about
10
o
F. If both the Leaving and Return water sensors are unreliable, the compressor is forced to 0%.
Zone Temperature (optional Zone Temperature Sensor)
When selected, a Zone Temperature Sensor is connected to TB-7 terminals #134 and #135. Four
variables are used to setup the reset ramp that calculates the Actual Leaving Water Setpoint. These
are: Leaving Water Dial Setpoint (AI-4), Reset Band SP selected with the Zone Terminal, Zone
Temperature High Limit (ZTHL), and Zone Temperature Reset Band (ZTRB).
Summary of Contents for AGZ 035A
Page 6: ...6 AGZ 035A through 065A IOMM AGZ 3 Figure 3 Clearance Requirements...
Page 18: ...18 AGZ 035A through 065A IOMM AGZ 3 Electrical Legend Figure 8 Electrical Legend...
Page 19: ...IOMM AGZ 3 AGZ 035A through 065A 19 Figure 9 Typical Field Wiring with Global UNT Controller...
Page 21: ...IOMM AGZ 3 AGZ 035A through 065A 21 Figure 11 Single point Connection with FanTrol...
Page 22: ...22 AGZ 035A through 065A IOMM AGZ 3 Figure 12 Single point Connection with SpeedTrol...
Page 23: ...IOMM AGZ 3 AGZ 035A through 065A 23 Figure 13 Unit Control Schematic UNT...
Page 24: ...24 AGZ 035A through 065A IOMM AGZ 3 Figure 14 Staging Schematic UNT...
Page 25: ...IOMM AGZ 3 AGZ 035A through 065A 25 Figure 15 MicroTech Controller Schematic...
Page 26: ...26 AGZ 035A through 065A IOMM AGZ 3 Figure 16 Unit Control Schematic MicroTech...
Page 27: ...IOMM AGZ 3 AGZ 035A through 065A 27 Figure 17 Staging Schematic MicroTech...
Page 94: ...94 AGZ 035A through 065A IOMM AGZ 3 Notes...
Page 95: ......