IOMM AGZB1
AGZ 010B through 034B
57
SET UNIT SPs (7)
CLOCK
dd/mmm/yyyy
hh:mm:ss
SET UNIT SPs (8)
Units =
°
°
°
°
F/psi
Lang = ENGLISH
Refrig = Select Type
Units settings are only °F/psi at the present time. °C/kPa will be available later.
Lang (Language) settings can be only ENGLISH at present.
Refrig (Refrigerant) selection is done at the factory prior to shippment.
SET UNIT SPs (9)
Protocol = NONE
Ident Number=001
Baud Rate=9600
SET UNIT SPs (10)
Evaporator Refrig
Press Sensor
Offset= 00.0 psi
The pressure/temperature offsets on menus 10 through 13 correct the controller's display of
the parameters. The sensors used in these units have a high degree of repeatability but may
need correction (offset). An accurate pressure gauge or thermometer is used to determine
the correct temperature or pressure. A positive or negative offset value is then entered to
make the controller reading agree with the measured value.
SET UNIT SPs (11)
Condenser Refrig
Press Sensor
Offset= 00.0 psi
SET UNIT SPs (12)
Leaving Evaporator
Water Temp Sensor
Offset= 00.0
o
F
SET UNIT SPs (13)
Outside Ambient
Temperature Sensor
Offset= 00.0
o
F