52
AGZ 010B through 034B
IOMM AGZB1
Menu selection is initiated by pressing the MENU key that changes the display from a
regular data screen to a menu screen. Menu selections are then made using the arrow keys
according to labels on the right side of the display (the arrows are ignored). When the last
menu item is selected, the display changes to the selected data screen. An example follows
showing the selection of the “VIEW COMPRESSOR (n) screen.
Suppose the initial screen is as below or any other menu screen:
ALARM LOG
(data)
(data)
(data)
After pressing the
MENU
key, the top level menu screen will show:
< ALARM
< VIEW
< SET
After pressing the “
VIEW
” menu key, a menu screen will show:
VIEW < UNIT
< COMPRESSOR
< REFRIGRANT
< FANS
Selection of any of these will advance to the appropriate data menu. For example, after pressing the
“
REFRIGERANT
” menu button, the selected data screen will show:
VIEW REFRIG
PSI
°
°
°
°
F
SAT EVAP XXX.X XX.X
SAT COND XXX.X XX.X
The ARROW keys will automatically return to the “scroll” mode at this time.
Screen Definitions VIEW
This section contains information on each screen. The menu screens are in order of the
matrix in Figure 17, going from left to right and then down when there are sub-menus.
Many menus are self-explanatory.
VIEW UNIT
VIEW UNIT STATUS (1)
Unit = AUTO
Cool Stages=0
Evap Pump = RUN
Summary of Contents for AGZ 010BM
Page 67: ......