![McQuay AGZ 010BM Installation, Operation And Maintenance Manual Download Page 53](http://html.mh-extra.com/html/mcquay/agz-010bm/agz-010bm_installation-operation-and-maintenance-manual_1756094053.webp)
IOMM AGZB1
AGZ 010B through 034B
53
Unit states can be:
Auto
Off:Ice Mode Timer
Off:All Comps Disabled
Off:Unit Alarm
Off:Keypad Disable
Off:Remote Switch
Off:BAS Disable
Off:Unit Switch
Auto:High LWT Pulldn
Auto:Cycle Timers
Auto:Wait for load
Auto:OAT Lockout
Auto:Evap Recirc
Auto:Wait for flow
Auto:Pumpdown
Auto:Evap Press Low
Auto:Cond Press High
Off:Test Mode
as determined from the Unit State variable, the Unit Mode setpoint, the Unit Enable and the
presence of an alarm.
Pump states can be:
Off
Start
Run
VIEW UNIT STATUS (2)
Stg Up Delay=XXX sec
Stg Dn Delay=XXX sec
Ice Delay=xxhr XX mn
Ice delay line is only visible when in the ICE mode.
VIEW UNIT STATUS (3)
D.O. D.I.
12345678 123456
00000000 000000
VIEW UNIT TEMP (1)
Evap LWT = XX.X
°
°
°
°
F
Outside Amb = XX.X
°
°
°
°
F
LWT Target = XX.X
°
°
°
°
F
VIEW UNIT TEMP (2)
LWT Pulldn=XX.X
°
°
°
°
F/m
Control Band=XX.X
°
°
°
°
F
VIEW UNIT TEMP (3)
StgUp@ XX.X Dn@ XX.X
Start Unit @ XX.X
Shutdown Unit @ XX.X
See page 39 for an explanation of these settings.
VIEW COMPRESSORS
VIEW COMP#1 (1)
State = OFF LEAD
Cycle Timer: XXmin
Manual Disable
Cycle timer only visible when active. Manual Disable visible only when compressor is
disabled via manual enable setpoint.
Summary of Contents for AGZ 010BM
Page 67: ......