IOMM AGZB1
AGZ 010B through 034B
55
ALARM LOG (1)
High Condenser Press
hh:mm:ss d/mmm/yyyy
The last 25 alarms, either shutdown or limit, are shown in this menu with subsequent menus
stored under it. ARROW DOWN from this menu will go to the next-to-last alarm, ARROW
DOWN again will go to the second from last, and so on through the last 25 occurrences.
The screens are numbered (1), (2), (3), etc.
Screen Definitions – SET
Changing setpoints;
in general, setpoints are changed as follows:
1.
Select the desired menu by scrolling through SET menus with the UP and DOWN
ARROWS.
2.
When the desired menu is selected, select the desired entry by moving between lines
using the ENTER key.
3.
If a numerical value is being changed, use the INCREMENT key (UP ARROW) to
increase or the DECREMENT key (DOWN ARROW) to decrease the value of the
setpoint.
If a word type setpoint (for example, YES or NO) is to be selected, the choices are
loaded into the menu and selected by scrolling through the available setpoint options
using the UP ARROW key.
4.
Enter the desired value or word into the controller by pressing the SET key.
SET UNIT SETPOINTS (SP)
SET UNIT SPs (1)
Unit Enable=OFF
Mode=COOL
Source=KEYPAD
Unit Enable is an external signal or a keypad setting that keeps the unit off when the setting
is OFF and
allows
it to run if there is a call for cooling. The source for the signal is
selected in the 4
th
line and can be:
1.
KEYPAD, in which case the selection is made in line 2 and would be normally selected
as ON. This is the normal setting when no external signals are controlling the unit.
2.
SWITCHES, in which an external switch is wired across terminals #25 and #35. (See
wiring diagram page 27).
3.
NETWORK, used with BAS signal, which is wired to the three communication ports.
Unit Mode settings can be
1.
COOL, normal setting used with chilled water air-condition applications.
2.
COOL w/GLYCOL, used with low temperature, glycol applications. It allows a lower
LWT setpoint to be used.
3.
ICE w/GLYCOL, used with ice storage systems, allows changing from chilled glycol
operation to lower temperature ICE operation. In ICE, the unit runs at full load until
the ICE setpoint is reached, at which time the unit shuts off. A three-position switch
wired to terminals #28 and #38 initiates the change from glycol cooling to making ice.
(See wiring diagram on page 27.)
Summary of Contents for AGZ 010BM
Page 67: ......