Fan Automation
Cooling
Mode
a. Room temperature ≤ setting temperature, valve closes automatically, fan stops;
b. Room temperature ≥ setting tempe1
℃
, fan turned on in low speed;
c. Room temperature ≥ setting tempe2
℃
, fan turned on in medium speed;
d. Room temperature ≥ setting tempe3
℃
, fan turned on in high speed;
Heating
Mode
a. Room temperature ≥ setting temperature, valve closes automatically, fan stops;
b. Room temperature ≤ setting temperature -1
℃
, fan turned on in low speed;
c. Room temperature ≤ setting temperature -2
℃
, fan turned on in medium speed;
d. Room temperature ≤ setting temperature -3
℃
, fan turned on in high speed;
Note: Fan will operate only if the valve opens.
Parameter Setting
Power Failure Memory
Under the shutdown state, press & hold
will enter interface for power failure memory
selection
,
“
PAGE
”
displays. Press
or
to change setting value, then press “
M
” to confirm and
return.
After power failure:
000 (default) indicates device will be in shutdown state (“OFF”) when power on again;
001 indicates device will be in working interface when power on again;
002 indicates device will stay the status before power failure when power on again.
Temp. Calibration/ Temp. Setting Range
Under the shutdown state, press & hold
will enter interface for temperature calibration,
“
-ERR
”
displays. The calibration range is among -5.0 ~ +5.0
℃
.
Press
or
to change setting value, then press “
M
” save and enter interface for temp.
Range setting (0~99
℃
):
1. “-HI-” displays, the default value is 35
℃.
Press
or
can set the value;
2. Press “
M
” again, “-LO-”displays, the default value is 5
℃.
Press
or
can set the value;
3. Then press “
M
” to confirm and return to “OFF”.
Screen Brightness/ Fan continuously work/ Key-touch volume
Under the shutdown state, press & hold “
M
” will enter interface for screen brightness selection
(LED), Press
or
can choose: (press “M” to confirm the choice and enter into next setting)
111 indicates the screen will always be full bright when power on;
000 (default) indicates without button operation for a long time (15 seconds), the screen will be
half bright automatically.
Press “
M
” again will enter interface for Fan continuously work choice:
000 (default) indicates device will shutdown fan and valve if room temp. Reaches setting temp.;
001 indicates device will shutdown valve only if room temp. Reaches setting temp. The fan will
continuously work in low speed.