background image

© 2013 Pentair Technical Products

87976428

- 5 -

Bench Testing

To avoid possible damage to the air conditioner, it must be in 

an upright operating position for a minimum of five (5) minutes 

before functional testing is started.

CAUTION

When “bench testing the HIBOY® air conditioner before mounting to the electronic enclosure, follow the procedures 

outlined in the following paragraphs:

Make sure that the HIBOY® air conditioner is supported in a manner that assures free air flow out of and back 

into the openings which are located in the base tray.
Refer to nameplate for proper electrical current requirements, then connect the power cord to a properly 

grounded electrical outlet.

NOTE: Minimum circuit ampacity should be at least 125% of the amperage shown in the DESIGN 

DATA table. To prevent overloading, no other equipment should be connected to this circuit.

Make sure the unit has been in the upright operating position for at least five minutes.
Operate the air conditioner for five (5) or ten (10) minutes. No excessive noise or vibration should be evident 

during this run period. The condenser blower located in the rear section of the air conditioner, the evaporator 

or cool air blower located in the bottom of the unit, and the compressor should be running. To check cool air 

output, use a reliable air temperature measuring device. The cool air should be between 50 F (10 C) and 60 F 

(16 C) when room temperature is between 70 F (21 C) and 80 F (27 C).
You may remove the air inlet filter while checking the operation. The discharge line from the compressor 

(uninsulated line) should become very warm. Carefully touch this line to avoid possible burns. Condenser air 

temperatures should be warmer than normal room temperatures within a few minutes.
Mounted along the side of the compressor is the suction accumulator which is insulated to help avoid 

sweating or condensation buildup.
The compressor is provided with automatic reset thermal overload protection. This thermo switch is located 

and mounted inside the plastic enclosure clipped to the compressor. The only time this switch should operate 

is when the compressor overheats due to clogged or dirty inlet air filter, if ambient air temperatures exceed 

nameplate rating or if enclosure dissipated heat loads exceed the rated capacity of the air conditioner. The 

thermal overload switch will actuate and stop compressor operation. Blowers will continue to operate, 

however, and the compressor will not restart until the compressor has cooled to within the thermal overload 

cut-in temperature setting.

Summary of Contents for HB16 Series

Page 1: ...v I P N 10 1008 06 Protecting Electronics Exceeding Expectations Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEquipmentProtection com INS...

Page 2: ...bility for freight damages however we are ready to assist you in any way possible NOTE Some of the information in this manual may not apply if a special unit was ordered If additional drawings for a s...

Page 3: ...Do not attempt to operate the air conditioner while it is horizontal or on its side back or front The refrigeration compressor is filled with lubricating oil This will cause permanent damage to the a...

Page 4: ...oltage Hertz Full Load Amps Phase BTU Hr Maximum Ambient Temperature Maximum F Ambient Temperature Shipping Weight lb kg HB160816GXXX 115 50 60 18 8 20 4 1 7075 8133 131 145 66 HB160826GXXX 230 50 60...

Page 5: ...l air blower located in the bottom of the unit and the compressor should be running To check cool air output use a reliable air temperature measuring device The cool air should be between 50 F 10 C an...

Page 6: ...ust be of sufficient size to handle the air flow 25 in 2 minimum Keep in mind that reduction of air flow will impair air conditioner performance Also remember that this air is hot and relatively dirty...

Page 7: ...A 5 inch 13 mm inside diameter drain tube exists on the side of the air conditioner and must be routed over the side A pressure relief fitting has been provided to assist in venting any air blockage t...

Page 8: ...y frequent cleaning and or replacement the inlet filter will assure relatively clean air to pass through the condenser coil Dirty filters will hamper the optimum operating efficiency of the air condit...

Page 9: ...mended that power to the air conditioner be interrupted intentionally when abnormally high compressor operating temperatures cause automatic shut down of the unit The above described shut down is symp...

Page 10: ...r disposable filters and filter adhesive see parts list in Table 1 on page 12 1 Flush the filter with warm water from the exhaust side to the intake side DO NOT use caustics 2 After flushing allow fil...

Page 11: ...hnical Products 87976428 11 Dimensional Drawings 5 5 7851 1 2685 22 5 287 5 287 0 17 0 17 5 1 6 59 25 URQW 9LHZ 6LGH 9LHZ 5HDU 9LHZ 1 5 86 80 180 1 7 7 5 81 5 1 26 RWWRP 9LHZ XWRXW HB16 Models 8000 BT...

Page 12: ...Only 35 See Table 1 1 Switch Compressor Thermal Overload 38 See Table 1 1 Compressor 39 See Table 1 1 Power Cord 47 52 6028 00 1 Filter Dryer Refrigerant 48 52 6027 00 1 Valve Hot Gas By Pass 230V Onl...

Page 13: ...2013 Pentair Technical Products 87976428 13 Parts Exploded View...

Page 14: ...2013 Pentair Technical Products 87976428 14 Wiring Schematic...

Page 15: ...2013 Pentair Technical Products 87976428 15 Electrical Schematic...

Page 16: ...2013 Pentair Technical Products 87976428 16 Notes...

Page 17: ...2013 Pentair Technical Products 87976428 17 Notes...

Page 18: ...has not been designed with proper protective coatings and or options and is in an abnormal or corrosive environment voids the warranty Prolonged operation with dirty filters also voids the warranty S...

Page 19: ...ntair Technical Products in writing of any such claim or demand provided further that Pentair Technical Products shall have the right and option to undertake and control the entire defense of such cla...

Page 20: ...cal Products 87976428 Rev I P N 10 1008 06 Protecting Electronics Exceeding Expectations Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEqu...

Reviews: