Device name:
Defines the device name of the router which has to be unique within the
overall BACnet network.
Description:
Defines the BACnet description – a free descriptive text – of the router.
Location:
Defines the BACnet location – a free text for the installation location – of the
router.
Vendor identifier:
Manufacturer ID for unique identification of the device manufacturer
Vendor name:
Manufacturer name as unique designation of the device manufacturer
Model name:
Model description of the router.
Firmware revision:
Firmware version of the router software
APDU max length accepted:
Maximum telegram size in bytes
The following values are possible: 50, 206, 480, 1024 and 1476 bytes.
ADPU timeout:
This value in milliseconds defines the period of time after which a telegram
that requires confirmation is deemed to have failed in the absence of
confirmation. The default value is 3000 ms.
APDU retries:
This value defines how often a failed telegram is to be repeated. The default
value is 5.
APDU segmentation supported:
Possible values: 0-both, 1-transmit, 2-receive, 3-no
APDU max segments accepted:
Defines how many segments are accepted as a maximum.