Chapter 4
Start-up and operation
30
The security setting for a communication link specifies the minimum required
security for a communication:
• Plain-Non-Trusted
Unencrypted telegrams from a potentially unsafe source are accepted
and routed – as long as the checkbox "Disable non trusted routing" is not
checked.
• Plain-Trusted
Unencrypted telegrams from a network physically secured against external
access are accepted and routed.
• Signed-Trusted
Signed telegrams are accepted. Non-signed or incorrectly signed
telegrams are rejected without an error message.
• Encrypted-Trusted
Only encrypted telegrams are accepted. All other telegrams are either
discarded or acknowledged with a fault message as applicable. A
prerequisite for this is the "do not hide" option.
LAN name :
Defines the interface of the data link (LAN2 on UBR-02 only).
• LAN1
• LAN2
UDP port:
Defines the UDP port of the BACnet/IP network as a decimal figure. The
default value is 47808 ("0xBAC0" - hexadecimal).
IP mode:
Defines the router's IP mode for this datalink.
• Normal
Standard operating mode for a BACnet IP datalink
• BBMD
operating mode as "BACnet Broadcast Management Device":
• FD
Operating mode as foreign device
Summary of Contents for UBR-01 MK II
Page 57: ......