- 26 -
12 Loading the factory settings
NOTICE
Before you configure the device to its factory settings, you should note the following:
• Save your configuration first. After restoring the factory settings, all of your settings/
changes will be deleted.
• The IP address of the device is reset to the original IP address (192.168.0.100).
• You may also need to modify the network settings of the configuration PC accordingly.
• The device password is reset to its individual default password. The default password
can be found on the back of the unit.
• No USB stick/storage medium should be connected to the device.
Execution:
1.
Switch on the mbNET or press the
Reset
button.
2.
Wait until the LED
Rdy flashes green
.
3.
Press and hold the
Dial Out
button until LED
Fc4 is lit
.
4. Press the
Dial Out
button again => LED
Fc3 lights
up.
5.
Repeat step 4. => LED
FC2 lights
up.
6. Press the
Dial Out
=> button one last time, after approximately 10 - 20 sec.
LED
Fc3 flashes
.
When both the Pwr and Rdy LEDs light up, the mbNET is reset to its „factory settings at the
time of delivery” and can/must be reconfigured.