Maytag Amana APCH32441 Installation Instructions Manual Download Page 8

8

TERMINAL

THERMOSTAT

Red

R (24V)

Green

G (Fan)

Orange

O (Rev. Valve)

White

W1 (Heat, 2nd)*

Brown

W2 (Heat 3rd)*

Yellow

Y (Cool)

C (Blue)

C (Common)

*Optional field installed heat connections

Table 4

Internal Wiring:

A diagram detailing the internal wiring of this unit is located 

on the electrical box cover. If any of the original wire 

supplied with the appliance must be replaced, the wire 

gauge and insulation must be the same as the original 

wiring.

1.  For branch circuit wiring (main power supply to unit 

disconnect), the minimum wire size for the length of 

the run can be determined from Table 2 using the 

circuit ampacity found on the unit rating plate. From 

the unit disconnect to unit, the smallest wire size 

allowable in Table 4 may be used for the ampacity, as 

the Disconnect must be in sight of the unit.

2.  Wire size based on 60°C rated wire insulation and 30° 

C Ambient Temperature (86°F).

3.  For more than 3 conductors in a raceway or cable, 

see the N.E.C. for derating the ampacity of each 

conductor.

OPERATION

Start-Up Procedure and Checklist

Begin with power turned off at all disconnects.

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or in-

stalling this unit. Multiple power sources may 

be present. Failure to do so may cause proper-

ty damage, personal injury or death. 

Air Conditioner Start-up Procedure

1.  Turn thermostat system switch to “Cool,” and fan- 

switch to “Auto” and turn temperature setting as high 

as it will go.

2.  Inspect all registers and set them to the normal open 

position.

3.  Turn on the electrical supply at the disconnect.

4.  Turn the fan switch to the “ON” position. The blower 

should operate after a 10 second delay.

5.  Turn the fan switch to “Auto” position. The blower 

should stop after a 60 second delay.

6.  Slowly lower the cooling temperature until the unit 

starts. The compressor, blower and fan should now be 

operating. Allow the unit to run 10 minutes, make sure 

cool air is being supplied by the unit.

7.  Turn the temperature setting to the highest position, 

stopping the unit. The indoor blower will continue to 

run for 60 seconds.

8.  Turn the thermostat system switch to “OFF” and 

disconnect all power when servicing the unit.

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or in-

stalling this unit. Multiple power sources may 

be present. Failure to do so may cause proper-

ty damage, personal injury or death. 

Heat Pump Start-Up Procedure

1.  Check the cooling mode for the heat pump in the 

same manner as above. The reversing valve is 

energized when the thermostat is placed in the 

cooling position. A clicking sound should be noticeable 

from the reversing valve. By lowering the temperature 

setting to call for cooling, the contractor is energized.  

The compressor, blower and fan should then be 

running. After the cooling mode is checked out, turn 

the thermostat system switch to “OFF”.

2.  Turn the thermostat system switch to “HEAT” and fan 

switch to “AUTO”.

3.  Slowly raise the heating temperature setting. When 

the heating first stage makes contact, stop raising 

the temperature setting. The compressor, blower and 

fan should now be running with the reversing valve in 

the de-energized (heating) position. After giving the 

unit time to settle out, make sure the unit is supplying 

heated air.

4.  If the outdoor ambient is above 80°F, the unit may trip 

on its high pressure cutout when in heating mode. The 

compressor should stop. The heating cycle must be 

thoroughly checked, so postpone the test to another 

day when conditions are more suitable but-DO NOT 

FAIL TO TEST.

5.  If the outdoor ambient is low and the unit operates 

properly in the heating cycle, you may check the 

pressure cutout operation by blocking off the indoor 

return air until the unit trips. If unit operates properly 

in the heating cycle, raise the temperature setting 

until the heating second stage makes contact. 

Supplemental resistance heat, if installed should now 

come on. Make sure it operates properly.

NOTE: If outdoor thermostats are installed 

the outdoor ambient must be below the set 

point of these thermostats for the heaters 

to operate. It may be necessary to jumper 

these thermostats to check heater operation 

if outdoor ambient is mild.

6.  For thermostats with emergency heat switch, return 

to step 11. The emergency heat switch is located 

at the bottom of the thermostat. Move the switch to 

emergency heat. The heat pump will stop, the blower 

will continue to run, all heaters will come on and the 

thermostat emergency heat light will come on.

Summary of Contents for Amana APCH32441

Page 1: ...or repair the equipment specified in this manual without proper training may result in product damage property damage personal injury or death WARNING RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION All...

Page 2: ...y look the location over both the inside and outside of home Note any potential obstacles or problems that might be encountered as noted in this manual Choose a more suitable location if necessary IMP...

Page 3: ...inal tons of cooling Optional field installed heat kits are available in 5 8 10 15 and 20 KW The units can be easily installed in manufactured or modular homes with existing high static duct work The...

Page 4: ...letely unobstructed If units are to be located under an overhang there should be a minimum of 48 clearance and provisions made to deflect the warm discharge air out from the overhang Location Consider...

Page 5: ...ver the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport Remove wood struts moun...

Page 6: ...lenum Application A suitable plenum or square duct must be constructed The duct cross sectional area should be determined by industry duct sizing manuals or air duct calculators On ductwork exposed to...

Page 7: ...NFPA NO 70 1984 or latest edition by using ground lug in the control box DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE Fuses or HACR type circuit breakers may be used wher...

Page 8: ...er when servicing the unit WARNING HIGH VOLTAGE Disconnect all power before servicing or in stalling this unit Multiple power sources may be present Failure to do so may cause proper ty damage persona...

Page 9: ...upplemental heat Normally a Defrost cycle will take only 2 3 minutes unless system is low on charge or outdoor conditions are severe windy and cold The defrost control also provides for a 3 minute off...

Page 10: ...e heating requirement should there be a component failure of the heat pump such as a compressor or refrigerant leak etc Since the temperature of the liquid refrigerant in the outdoor coil on the heati...

Page 11: ...ple type temperature test lead on the tube adjacent to the defrost control Insulate the lead point of contact 2 Check the temperature at which the control closes its contacts by lowering the temperatu...

Page 12: ...or with a electronic control board ECM Motor The ECM motor provides many features not available on the traditional PSC motor These features include Improved Efficiency Constant CFM Soft Start and Stop...

Page 13: ...ltage power wire typically the black lead to the thermostat R Red wire in control box 5 Secure the dehumidistat ground wire typically the green lead to the ground screw to the unit s sheet metal contr...

Page 14: ...running on low stage with TXV application should have a subcooling and superheat within the range listed on the chart a If subcooling and superheat are low adjust TXV superheat then check subcooling N...

Page 15: ...to easily install the HKR HKP Series Electric Heat Kit Full Installation Instructions are included in this kit Please use this document for guidance in field equipping the package unit with electric h...

Page 16: ...Do not allow air entering the indoor coil to drop below 65 F Air below this temperature will cause low discharge pressure thus low suction pressure and excessive defrost cycling resulting in low heati...

Page 17: ...88 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674 1637 1596 1557 1518 1474 Watts 394 406 418 430 443 455 466 474 CFM 2002 1935 1885 1827 1767 1732 1669 1618 Watts 498 521 516 534 55...

Page 18: ...gs for Single Two Stage Thermostat Speed Tap Switch 5 Switch 6 A OFF OFF B ON OFF C OFF ON D ON ON Cooling HP DIP Switch Settings CFM Switch 7 Switch 8 Plus 10 ON OFF Normal OFF OFF Minus 10 OFF ON Sp...

Page 19: ...81 294 305 318 330 CFM 1736 1679 1638 1598 1558 1520 1484 1441 Watts 356 372 382 395 408 422 433 442 CFM 1337 1297 1218 1155 1118 1088 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674...

Page 20: ...t be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective replace Low suction cool compressor a a Iced evaporator coil a Defective overlo...

Page 21: ...A B PCH32441 66 34 27 30 Small PCH33041 66 34 27 30 Small PCH33641 66 34 27 30 Small PCH34241 66 34 32 35 Medium PCH34841 66 34 32 35 Medium PCH36041 66 34 32 35 Medium Model Duct Openings Supply Ret...

Page 22: ...A B PHH32441 66 34 27 30 Small PHH33041 66 34 27 30 Small PHH33641 66 34 32 35 Medium PHH34241 66 34 32 35 Medium PHH34841 66 34 32 35 Medium PHH36041 66 34 36 38 Large Model Duct Openings Supply Ret...

Page 23: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Page 24: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 25: ...25 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 26: ...26 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 27: ...27 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 28: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Reviews: