Maytag Amana APCH32441 Installation Instructions Manual Download Page 16

16

APCH36041 Models

See “Blower Performance” section for Electric Heat DIP 

Switch settings.

MAINTENANCE

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or in-

stalling this unit. Multiple power sources may 

be present. Failure to do so may cause proper-

ty damage, personal injury or death. 

The Self Contained Package Air Conditioner and Heat 

Pump should operate for many years without excessive 

service calls if the unit is installed properly. However it 

is recommended that the homeowner inspect the unit 

before a seasonal start up. The coils should be free of 

debris so adequate airflow is achieved. The return and 

supply registers should be free of any obstructions. The 

filters should be cleaned or replaced. These few steps 

will help to keep the product up time to a maximum. 

The Troubleshooting Chart (on page 16) should help in 

identifying problems if the unit does not operate properly.

SERVICE

THE FOLLOWING INFORMATION IS FOR USE BY 

QUALIFIED SERVICE AGENCY ONLY: OTHERS 

SHOULD NOT ATTEMPT TO SERVICE THIS 

EQUIPMENT.

Common Causes of Unsatisfactory Operation of Heat 

Pump on the Heating Cycle.

Inadequate Air Volume Through Indoor Coil 

When a heat pump is in the heating cycle, the indoor coil 

is functioning as a condenser. The return air filter must 

always be clean, and sufficient air volume must pass 

through the indoor coil to prevent excessive discharge 

pressure, and high pressure cut out.

Outside Air Into Return Duct 

Do not introduce cold outside air into the return duct of a 

heat pump installation. Do not allow air entering the indoor 

coil to drop below 65°F. Air below this temperature will 

cause low discharge pressure, thus low suction pressure, 

and excessive defrost cycling resulting in low heating 

output. It may also cause false defrosting.

Undercharge 

An undercharged heat pump on the heating cycle will 

cause low discharge pressure resulting in low suction 

pressure and frost accumulation on the outdoor coil.

Poor “Terminating” Sensor Contact 

The unit’s defrost terminating sensor must make good 

thermal contact with the outdoor coil tubing. Poor contact 

may not terminate the unit’s defrost cycle quickly enough 

to prevent the unit from cutting out on high discharge 

pressure.

Malfunctioning Reversing Valve 

This may be due to:

1.  Solenoid not energized

 - In order to determine if the 

solenoid is energized, touch the nut that holds the 

solenoid cover in place with a screwdriver. If the nut 

magnetically holds the screwdriver, the solenoid is 

energized and the unit is in the cooling cycle.

2.  No voltage at unit’s solenoid 

- Check unit voltage. If 

no voltage, check wiring circuit.

3.  Valve will not shift:

a.  Undercharged

 - check for leaks;

b.  Valve Body Damaged 

- Replace valve;

c.  Unit Properly Charged 

- If it is on the heating 

cycle, raise the discharge pressure by restricting 

airflow through the indoor coil. If the valve 

does not shift, tap it lightly on both ends with 

a screwdriver handle. Do Not Tap The Valve 

Body. If the unit is on the cooling cycle, raise the 

discharge pressure by restricting airflow through 

the outdoor coil. If the valve does not shift after 

the above attempts, cut the unit off and wait until 

the discharge and suction pressure equalize, and 

repeat above steps. If the valve does not shift, 

replace it.

Summary of Contents for Amana APCH32441

Page 1: ...or repair the equipment specified in this manual without proper training may result in product damage property damage personal injury or death WARNING RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION All...

Page 2: ...y look the location over both the inside and outside of home Note any potential obstacles or problems that might be encountered as noted in this manual Choose a more suitable location if necessary IMP...

Page 3: ...inal tons of cooling Optional field installed heat kits are available in 5 8 10 15 and 20 KW The units can be easily installed in manufactured or modular homes with existing high static duct work The...

Page 4: ...letely unobstructed If units are to be located under an overhang there should be a minimum of 48 clearance and provisions made to deflect the warm discharge air out from the overhang Location Consider...

Page 5: ...ver the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport Remove wood struts moun...

Page 6: ...lenum Application A suitable plenum or square duct must be constructed The duct cross sectional area should be determined by industry duct sizing manuals or air duct calculators On ductwork exposed to...

Page 7: ...NFPA NO 70 1984 or latest edition by using ground lug in the control box DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE Fuses or HACR type circuit breakers may be used wher...

Page 8: ...er when servicing the unit WARNING HIGH VOLTAGE Disconnect all power before servicing or in stalling this unit Multiple power sources may be present Failure to do so may cause proper ty damage persona...

Page 9: ...upplemental heat Normally a Defrost cycle will take only 2 3 minutes unless system is low on charge or outdoor conditions are severe windy and cold The defrost control also provides for a 3 minute off...

Page 10: ...e heating requirement should there be a component failure of the heat pump such as a compressor or refrigerant leak etc Since the temperature of the liquid refrigerant in the outdoor coil on the heati...

Page 11: ...ple type temperature test lead on the tube adjacent to the defrost control Insulate the lead point of contact 2 Check the temperature at which the control closes its contacts by lowering the temperatu...

Page 12: ...or with a electronic control board ECM Motor The ECM motor provides many features not available on the traditional PSC motor These features include Improved Efficiency Constant CFM Soft Start and Stop...

Page 13: ...ltage power wire typically the black lead to the thermostat R Red wire in control box 5 Secure the dehumidistat ground wire typically the green lead to the ground screw to the unit s sheet metal contr...

Page 14: ...running on low stage with TXV application should have a subcooling and superheat within the range listed on the chart a If subcooling and superheat are low adjust TXV superheat then check subcooling N...

Page 15: ...to easily install the HKR HKP Series Electric Heat Kit Full Installation Instructions are included in this kit Please use this document for guidance in field equipping the package unit with electric h...

Page 16: ...Do not allow air entering the indoor coil to drop below 65 F Air below this temperature will cause low discharge pressure thus low suction pressure and excessive defrost cycling resulting in low heati...

Page 17: ...88 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674 1637 1596 1557 1518 1474 Watts 394 406 418 430 443 455 466 474 CFM 2002 1935 1885 1827 1767 1732 1669 1618 Watts 498 521 516 534 55...

Page 18: ...gs for Single Two Stage Thermostat Speed Tap Switch 5 Switch 6 A OFF OFF B ON OFF C OFF ON D ON ON Cooling HP DIP Switch Settings CFM Switch 7 Switch 8 Plus 10 ON OFF Normal OFF OFF Minus 10 OFF ON Sp...

Page 19: ...81 294 305 318 330 CFM 1736 1679 1638 1598 1558 1520 1484 1441 Watts 356 372 382 395 408 422 433 442 CFM 1337 1297 1218 1155 1118 1088 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674...

Page 20: ...t be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective replace Low suction cool compressor a a Iced evaporator coil a Defective overlo...

Page 21: ...A B PCH32441 66 34 27 30 Small PCH33041 66 34 27 30 Small PCH33641 66 34 27 30 Small PCH34241 66 34 32 35 Medium PCH34841 66 34 32 35 Medium PCH36041 66 34 32 35 Medium Model Duct Openings Supply Ret...

Page 22: ...A B PHH32441 66 34 27 30 Small PHH33041 66 34 27 30 Small PHH33641 66 34 32 35 Medium PHH34241 66 34 32 35 Medium PHH34841 66 34 32 35 Medium PHH36041 66 34 36 38 Large Model Duct Openings Supply Ret...

Page 23: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Page 24: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 25: ...25 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 26: ...26 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 27: ...27 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 28: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Reviews: