Maytag Amana APCH32441 Installation Instructions Manual Download Page 5

5

2.  Make proper consideration for the weather-tight 

integrity of the roof and proper drainage of condensate.

3.  To ensure proper condensate drainage, unit must be 

installed in a level position.

4.  Consideration should also be given to shade, 

appearance and noise.   

36"

36"

24"

PL

EN

UM

UNI

T

PL

AT

FOR

M

CU

RB

Figure 2

RIGGING

Rigging Details

WARNING

To prevent property damage, the unit should remain in an 

uprght position during all rigging and moving operations. To 

facilitate lifting and moving when a crane is used, place the 

unit in an adequate cable sling.

CAUTION

If units are lifted two at a time, the fork holes on the 

condenser end of the unit must not be used. Minimum fork 

length is 42” to prevent damage to the unit; however, 48” is 

recommended.

NOTE: Provisions for forks have been included in 

the unit base frame. No other fork locations are 

approved.

WARNING

To prevent possible equipment damage, property damage, per-

sonal injury or death, the following bullet points must be 

observed when installing the unit.

Unit must be lifted by the four lifting holes located at the 

base frame corners.

•   Lifting cables should be attached to the unit with 

shackles.

•   The distance between the crane hook and the top of 

the unit must not be less than 60”.

•   Two spreader bars must span over the unit to prevent 

damage to the cabinet by the lift cables. Spreader 

bars must be of sufficient length so that cables do 

not come in contact with the unit during transport. 

Remove wood struts mounted beneath unit base 

frame before setting unit on roof curb. These struts 

are intended to protect unit base frame from fork lift 

damage. Removal is accomplished by extracting the 

sheet metal retainers and pulling the struts through 

the base of the unit. Refer to rigging label on the unit.

Refer to the Roof Curb Installation Instructions for proper 

curb installation. Curbing must be installed in compliance 

with the National Roofing Contractors Association Manual.

Figure 3

WARNING

Do not, under any circumstances, connect return ductwork 

to any other heat producing devices such as a fireplace 

insert, stove, etc. Unauthorized use of such devices may 

result in property damage, fire, carbon monoxide poisoning, 

explosion, personal injury or death.

DUCTING

Ducting work should be fabricated by the installing 

contractor in accordance with local codes. Industry 

manuals may be used as a guide when sizing and 

designing the duct system- such as NESCA (National 

Environmental Systems Contractors Association, 1501 

Wilson Blvd., Arlington, Virginia 22209). 

The unit should be placed as close as possible to the 

space to be air-conditioned allowing clearance dimensions 

as indicated. Ducts should run as directly as possible 

to supply and return outlets. Use of non-flammable 

Summary of Contents for Amana APCH32441

Page 1: ...or repair the equipment specified in this manual without proper training may result in product damage property damage personal injury or death WARNING RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION All...

Page 2: ...y look the location over both the inside and outside of home Note any potential obstacles or problems that might be encountered as noted in this manual Choose a more suitable location if necessary IMP...

Page 3: ...inal tons of cooling Optional field installed heat kits are available in 5 8 10 15 and 20 KW The units can be easily installed in manufactured or modular homes with existing high static duct work The...

Page 4: ...letely unobstructed If units are to be located under an overhang there should be a minimum of 48 clearance and provisions made to deflect the warm discharge air out from the overhang Location Consider...

Page 5: ...ver the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport Remove wood struts moun...

Page 6: ...lenum Application A suitable plenum or square duct must be constructed The duct cross sectional area should be determined by industry duct sizing manuals or air duct calculators On ductwork exposed to...

Page 7: ...NFPA NO 70 1984 or latest edition by using ground lug in the control box DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE Fuses or HACR type circuit breakers may be used wher...

Page 8: ...er when servicing the unit WARNING HIGH VOLTAGE Disconnect all power before servicing or in stalling this unit Multiple power sources may be present Failure to do so may cause proper ty damage persona...

Page 9: ...upplemental heat Normally a Defrost cycle will take only 2 3 minutes unless system is low on charge or outdoor conditions are severe windy and cold The defrost control also provides for a 3 minute off...

Page 10: ...e heating requirement should there be a component failure of the heat pump such as a compressor or refrigerant leak etc Since the temperature of the liquid refrigerant in the outdoor coil on the heati...

Page 11: ...ple type temperature test lead on the tube adjacent to the defrost control Insulate the lead point of contact 2 Check the temperature at which the control closes its contacts by lowering the temperatu...

Page 12: ...or with a electronic control board ECM Motor The ECM motor provides many features not available on the traditional PSC motor These features include Improved Efficiency Constant CFM Soft Start and Stop...

Page 13: ...ltage power wire typically the black lead to the thermostat R Red wire in control box 5 Secure the dehumidistat ground wire typically the green lead to the ground screw to the unit s sheet metal contr...

Page 14: ...running on low stage with TXV application should have a subcooling and superheat within the range listed on the chart a If subcooling and superheat are low adjust TXV superheat then check subcooling N...

Page 15: ...to easily install the HKR HKP Series Electric Heat Kit Full Installation Instructions are included in this kit Please use this document for guidance in field equipping the package unit with electric h...

Page 16: ...Do not allow air entering the indoor coil to drop below 65 F Air below this temperature will cause low discharge pressure thus low suction pressure and excessive defrost cycling resulting in low heati...

Page 17: ...88 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674 1637 1596 1557 1518 1474 Watts 394 406 418 430 443 455 466 474 CFM 2002 1935 1885 1827 1767 1732 1669 1618 Watts 498 521 516 534 55...

Page 18: ...gs for Single Two Stage Thermostat Speed Tap Switch 5 Switch 6 A OFF OFF B ON OFF C OFF ON D ON ON Cooling HP DIP Switch Settings CFM Switch 7 Switch 8 Plus 10 ON OFF Normal OFF OFF Minus 10 OFF ON Sp...

Page 19: ...81 294 305 318 330 CFM 1736 1679 1638 1598 1558 1520 1484 1441 Watts 356 372 382 395 408 422 433 442 CFM 1337 1297 1218 1155 1118 1088 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1758 1715 1674...

Page 20: ...t be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective replace Low suction cool compressor a a Iced evaporator coil a Defective overlo...

Page 21: ...A B PCH32441 66 34 27 30 Small PCH33041 66 34 27 30 Small PCH33641 66 34 27 30 Small PCH34241 66 34 32 35 Medium PCH34841 66 34 32 35 Medium PCH36041 66 34 32 35 Medium Model Duct Openings Supply Ret...

Page 22: ...A B PHH32441 66 34 27 30 Small PHH33041 66 34 27 30 Small PHH33641 66 34 32 35 Medium PHH34241 66 34 32 35 Medium PHH34841 66 34 32 35 Medium PHH36041 66 34 36 38 Large Model Duct Openings Supply Ret...

Page 23: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Page 24: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 25: ...25 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 26: ...26 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 27: ...27 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 28: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Reviews: