Troubleshooting and remedies

Fault indication

Possible cause

Remedy

Yellow “S1” LED and red 

“F” LED are flashing

Sensor not connected (or not connect-

ed correctly) to terminals Y1 and Y2

 

Ä

Connect sensor

Sensor 1 cable break

1.  Measure resistance at sensor 1: target 

value = 8k2 ±5% or 10k ±5%

2.  Actual value > 1M: sensor is faulty
3.  Replace sensor
4.  Disconnect power supply for at least 

500 ms

Yellow “S2” LED and red 

“F” LED are flashing

Sensor not connected (or not connect-

ed correctly) to terminals Y3 and Y4

 

Ä

Connect sensor

Sensor 2 cable break

1.  Measure resistance at sensor 2: target 

value = 8k2 ±1% or 10k ±1%

2.  Actual value > 1M: sensor is faulty
3.  Replace sensor
4.  Disconnect power supply for at least 

500 ms

Green “P”, yellow “S1” 

and/or yellow “S2” LEDs 

are lit up

Automatic

 reset: bridges missing

 

Ä

Place bridges between S13 and S15 as 

well as between S14 and S15

Controlled

 reset: no reset signal from 

higher-level control or pulse duration 

is too short

 

Ä

Trigger a signal pulse from the control 

system (≥ 70 ms)

Controlled reset: connection to control 

interrupted

 

Ä

Check connection

Manual

 reset: reset button not 

pressed or not held down long 

enough

 

Ä

Press reset button (≥ 70 ms)

Manual reset: connection to reset but-

ton interrupted

 

Ä

Check connection

Control unit is faulty

 

Ä

Replace control unit

Green “P”, yellow “S1” 

and yellow “S2” LEDs 

are lit up, red “F” LED 

flashes

Controlled or manual reset: duration 

of signal pulse from higher-level 

control is too long or reset button is 

jammed

1.  Check the duration of the signal pulse 

(≤ 19 s) from the higher-level control 

or replace the reset button at S13 and 

S14

2.  Disconnect power supply for at least 

500 ms

Control unit is faulty

 

Ä

Replace control unit

Still unable to resolve the fault?

 

Ä

Contact Mayser-Support: Tel. +49 731 2061-0.

 

Ä

In the event of enquiries, have the information from the type plate to hand.

Type plate

There is a type plate on the side of the control unit for identification purposes.

Summary of Contents for 1006747

Page 1: ...ions Mayser GmbH Co KG rlinger Strasse 1 3 89073 Ulm GERMANY Tel 49 731 2061 0 Fax 49 731 2061 222 E mail info ulm mayser com Website www mayser com Innovative by tradition 1006747 SG RS 309 2 24 to 3...

Page 2: ...he product Add any supplement received from the manufacturer to the instruc tions Observe the information under Safety starting on page 5 Conformity The Declaration of Conformity is available in the D...

Page 3: ...omatic reset 9 Controlled reset 9 Manual reset 10 Installation 11 Reset 12 Automatic reset 12 Controlled reset 12 Manual reset 12 Signal outputs 13 Connection examples 13 Commissioning 15 Testing the...

Page 4: ...e environ ment Information on easier and safer working practices Other applicable documents Please also observe the following documents Drawing of the sensor system optional Wiring diagram optional In...

Page 5: ...oid electrical injuries For your own safety you must adhere to the following safety instructions Take care when setting up the interface Overall safety is affected by the quality and reliability of th...

Page 6: ...d to the connecting voltage US specified on the type plate Observe correct terminal assignment Observe the correct terminal assignment when connecting the supply volt age Do not overload control unit...

Page 7: ...gnal output Monitoring circuit 2 sensor 2 22 Semiconductor output OSSD 2 1 42 Semiconductor output OSSD 2 2 M2 Signal output 11 14 31 34 Without function 21 24 41 44 Without function Parts supplied 1...

Page 8: ...ut M2 is HIGH The yellow LED S2 is lit up If sensor 1 and sensor 2 are activat ed then the OSSDs from monitoring circuit 1 and monitoring circuit 2 are in OFF state signal outputs M1 and M2 are HIGH T...

Page 9: ...OSSDs remain in OFF state The control unit is now in the mode Monitoring circuit 2 inactive If the defined signal pulse of the higher level control is applied to terminal S14 the OSSDs change from th...

Page 10: ...u ation period The conditions for this are Min max actuation period 70 ms 19 s If the actuation period is shorter than the minimum permitted no reset will take place If the max actuation period is exc...

Page 11: ...connect from the power supply all devices and live parts that are located in the immediate vicinity Secure them to prevent them being switched back on Check that they are de energised Caution Impaired...

Page 12: ...HIGH state ON state the voltage US 0 7 V is applied depending on the load and supply voltage The following applies to the outputs Wire the load between the output terminal and A2 Place bridges betwee...

Page 13: ...wing applies to the signal outputs Wire the load between the signal output terminal and A2 Connection examples Connection example 1 Connection example 2 Signal outputs Monitoring circuit 1 Monitoring...

Page 14: ...S 309 2 Page 14 23 Installation Monitoring circuit 1 Monitoring circuit 2 Reset Connection example 3 Connection example 4 Manual reset Contact multiplication Controlled reset Monitoring circuit 1 Moni...

Page 15: ...onnected activate sensor 2 Yellow S2 LED is lit up OSSDs from monitoring circuit 2 are in the OFF state Signal output M2 is set to HIGH 5 Repeat step 1 6 Disconnect sensor 1 Yellow S1 LED and red F LE...

Page 16: ...reset button Green P LED is lit OSSDs from monitoring circuits 1 and 2 are in the ON state Signal outputs M1 and M2 are set to LOW 3 Activate sensor 1 Yellow S1 LED is lit up OSSDs from monitoring ci...

Page 17: ...step 1 13 Interrupt the power supply for at least 500 ms The control unit will restart 14 Repeat step 2 Throughout the entire time the protective device remains activated the OSSDs stay in the OFF st...

Page 18: ...FF HIGH HIGH Fault or system error OFF ON or ON OFF OFF HIGH HIGH Fault on monitoring circuit 1 OSSD 1 1 OFF state and 1 2 ON state or OSSD 1 1 ON state and 1 2 OFF state OFF OFF ON or ON OFF HIGH HIG...

Page 19: ...8k2 or 10k resistor to terminals Y1 Y2 2 Fault not rectified replace control unit Yellow S2 LED is lit up Sensor 2 is faulty 1 Measure resistance at sensor 2 target value 8k2 5 or 10k 5 2 Actual valu...

Page 20: ...s between S14 and S15 Controlled reset no reset signal from higher level control or pulse duration is too short Trigger a signal pulse from the control system 70 ms Controlled reset connection to cont...

Page 21: ...he devices may be returned to us for disposal WEEE reg no DE 39141253 Disposal Control unit Packaging Wood cardboard plastics When disposing of the product Ensure compliance with the relevant national...

Page 22: ...lag Times Reaction time ta 15 ms Start time max 2 s Restart time tw 150 ms Safety classifications ISO 13856 Reset function With without ISO 13849 1 2015 Category 3 PL d MTTFD 937 a DCavg 92 nop assump...

Page 23: ...or 2 0 34 mm2 with plastic sleeve 1 0 5 mm2 or TWIN 0 5 mm2 IEC 60529 Degree of protection IP20 EN 50124 Pollution degree PD2 Max humidity 23 C 95 EN 50125 Class of altitude range A1 Operating temper...

Reviews: