121022 v1.02-RiA
Operating instructions SG-RS 309-2
Page 15/23
Commissioning
1. Make sure that everything is connected and no sensor is activated.
-
Green “P” LED is lit
-
OSSDs from monitoring circuit 1 and monitoring circuit 2 are in the ON
state
-
Signal outputs M1 and M2 are set to LOW
2. Activate sensor 1.
-
Yellow “S1” LED is lit up
-
OSSDs from monitoring circuit 1 are in the OFF state
-
Signal output M1 is set to HIGH
3. Repeat step 1.
4. If connected, activate sensor 2.
-
Yellow “S2” LED is lit up
-
OSSDs from monitoring circuit 2 are in the OFF state
-
Signal output M2 is set to HIGH
5. Repeat step 1.
6. Disconnect sensor 1.
-
Yellow “S1” LED and red “F” LED are flashing
-
OSSDs from monitoring circuits 1 and 2 are in the OFF state
-
Signal outputs M1 and M2 are set to HIGH
7. Repeat step 1.
8. Interrupt the power supply for at least 500 ms.
The control unit will restart.
Commissioning
1. Make sure the plug connections are firmly attached.
2. Connect the supply voltage.
Automatic reset
WARNING Danger of injury from electric shock
Ä
Never unplug plug-in connectors while live.
Testing the function