background image

 

 

detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) 
shall not be used. 

6 LEAK DETECTION METHODS 

The following leak detection methods are deemed acceptable for systems containing 
flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, 
but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be 
calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of 
ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a 
percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and 
the appropriate percentage  of gas (25 % maximum) is confirmed.  Leak detection fluids are 
suitable for use with  most refrigerants but the use of detergents  containing chlorine shall be 
avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak 
is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found 
which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by 
means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) 
shall then be purged through the system both before and during the brazing process. 

7 REMOVAL AND EVACUATION 

When breaking into the refrigerant circuit to make repairs – or for any other purpose – con- 
ventional procedures shall be used.However, it is important that best practice is followed 
since flammability is a consideration. The following procedure shall be adhered to: remove 
refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas; open the circuit 
by cutting or brazing.The refrigerant charge shall be recovered into the correct recovery cylinders. 
The system  shall be “flushed” with OFN to render the unit  safe. This process may need to be 
repeated several times.Compressed air or oxygen shall not be used for this task. Flushing shall 
be  achieved by breaking the vacuum in the  system with OFN and continuing to fill until the 
working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. 
This process shall be repeated until  no refrigerant is within the system. When the  final OFN 
charge is used, the system shall be vented down to atmospheric pressure to enable work to take 
place.This operation is absolutely vital if brazing operations on the pipework are to take place. 
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 
ventilation available. 

8 CHARGING PROCEDURES 

In addition to conventional charging procedures,the following requirements shall be followed. 
-  Ensure that contamination of different refrigerants does not occur when using charging 
equipment. Hoses or lines shall be as  short as possible to minimise the amount of  refrigerant 
contained in them. 
- Cylinders shall be kept upright. 
- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. 
- Label the system when charging is complete (if not already). 
- Extreme care shall be taken not to overfill the refrigeration system. 
Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak 
tested on completion of charging but prior to commissioning. A follow up leak test shall be 
carried out prior to leaving the site. 

9 DECOMMISSIONING 

Before carrying out this procedure, it is essential that the technician is completely familiar 
with the equipment and all its detail. It is  recommended good practice that all refrigerants are 

Summary of Contents for 20737

Page 1: ...Portable Air Conditioner Model 20737 20738 User s Manual...

Page 2: ...stallation Contents 1 Safety Awareness 1 2 Name of Parts 12 3 Accessories 12 4 Appearance and Function of Control Panel 13 5 Appearance and Function of Remote Control 13 6 Operation Introduction 14 7...

Page 3: ...pliance or an operating electric heater Do not pierce or burn Be aware the refrigerants may not contain an odour Appliance shall be installed operated and stored in a room with a floor area larger tha...

Page 4: ...fic evaluation recognized by associations in the industry Repairs must be performed based on the recommendation from the manufacturing company Maintenance and repairs that require the assistance of ot...

Page 5: ...all not be made by children without supervision 13 The appliance shall be installed in accordance with national wiring regulations 14 Details of type and rating of fuses T 250V AC 2A or higher 15 Recy...

Page 6: ...he person competent in the use of flammable refrigerants 22 Do not operate or stop the unit by inserting or pulling out Die power plug it may cause electric shock or fire due to heat generation 23 Unp...

Page 7: ...der or CO 2 fire extinguisher adjacent to the charging area 1 6 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contain...

Page 8: ...to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation...

Page 9: ...with inert gas open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushed with OFN to render the unit safe This pr...

Page 10: ...bel shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 11 RECOVERY When removing refrigerant from a system either for servicin...

Page 11: ...that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure is opened Ventilated enclosure see Clause GG 4 Safety of the appliance depend...

Page 12: ...before putting into service d Decommissioning If the safety is affected when the equipment is putted out of service the refrigerant charge shall be removed before decommissioning Ensure sufficient ve...

Page 13: ...l required signs are to be maintained and employers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions tha...

Page 14: ...essories are included and check their purposes in the installation introduction in this manual Part Description Quantity Main Air conditioner Unit 1 Hot air exhaust hose 1 Hose Connector Window end 1...

Page 15: ...ly model 5 Appearance and Function of Remote Control 4 Appearance and Function of Control Panel 5 Appearance and Function of Remote Control Fan speed selector Mode selector Hourly programming Temperat...

Page 16: ...sed to direct sunlight 6 Operation Introduction Before starting operations in this section 1 Find a place where there is power supply nearby 2 As shown in Fig 6 and Fig 6a install the exhaust hose and...

Page 17: ...rements The socket is for AC use Do not share one socket with other appliances Power supply is AC220 240V 50Hz 2 Cooling operation Press the Mode button till the Cool icon appears Press the or button...

Page 18: ...ainage hole at the bottom of unit and drain all water outside You can use the continuous drainage with a drainage hose connected to the bottom drain hole when the unit working at the HEAT mode The con...

Page 19: ...xing clip and the flat fixing clip 2 Insert the square fixing clip into openings at back of the air conditioner see Fig 9 3 Put the other end of the exhaust hose to the near windowsill Window Slider K...

Page 20: ...ll indicator lamp lights up If water pump is damaged when the water is full please remove the rubber blockage at the bottom of unit and all water will drain outside 8 Maintenance Explanations Declarat...

Page 21: ...p in the shade Mounting Putting the air filter into the inlet grille replace the components as they were 2 Clean the Air conditioner Surface First clean the surface with a neutral detergent and wet cl...

Page 22: ...ed Connect or clean the exhaust air hose Temperature setting is too high Reset the temperature Air inlet is blocked Clean the air inlet 3 Noisy The ground is not level or not flat enough Place the uni...

Page 23: ...21 6 E3 Code Evaporator temperature sensor failed Replace evaporator temperature sensor 7 E4 Code Water tank full when heating Please empty the water tank Note The real products may look different...

Page 24: ...rdelen en handleidingen Heb je vragen of klachten contacteer ons en we helpen je graag verder NOTRE EQUIPE MAXXTOOLS VOUS AIDERA VOLONTI RE AUX CAS SUIVANTS n Questions sur votre commande n R clamatio...

Reviews: