7. ELECTRICAL INSTALLATION

Please follow all electrical instructions carefully. This appliance must be installed by a licensed and 
qualified electrician in accordance with all applicable national, state, provincial, and local electrical codes.

All wiring (wire gages), circuit breakers (protector), must comply with the US National Electrical Code 
(NEC), in the USA, or the Canadian Electrical Code (CEC). Failure to do so could result in property 
damage and/or personal injury and void your warranty.

The Canadian electrical code generally requires all wires and corresponding circuit breakers used to install 
tankless water heaters shall be sized to a minimum of 125% of the maximum current rating of the water 
heater. (See model specifications and details below).

Before installing this appliance make sure the house has sufficient electrical power available to handle the 
maximum amperage load of the applicable model of your heater.

A. 

Make sure all power sources to the unit are disconnected before doing any connection to the terminal box 

and working with it. Follow the wiring diagrams based on the unit you have purchased. All mounting and 
plumbing installation must be completed before proceeding with the electrical installation.

B-1. MS120C2T_U must be connected to a single double pole breaker. Read all name plates carefully and wire as 
per instructions, and table 1.

Required Breaker Size to be installed in the main electrical panel

Model No.

MS120

MS150

MS 180

MS210

MS240

MS270

Breakers for 

Main 

Elecrical 
Panel 
Without the 
Sub-panel

Qty. 1 

Double 

Pole 
60 A

Qty. 2 

Double 

Pole 
50 A

Qty. 2 

Double 

Pole 
50 A

Qty. 3 

Double 

Pole 
40 A

Qty. 3 

Double 

Pole 
40 A

Qty. 3 

Double 

Pole 
50 A

Check your local electrical code requirements for different voltage applications 

Amperage requirementes are based on 240 v

Table 3

Summary of Contents for MSxxxC2T series

Page 1: ...r Heater Installation and Instructions Manual Keep this Instructions Manual in a safe place once your unit is installed You may need to refer to it for general instructions or future maintenance MSxxxC2T_U SERIES MSxxxC2TMU ...

Page 2: ... 4 270 21 0 B Injection Molding Black S Injection Molding Silver W Injection Molding White M Metal Casing Silver CONTENTS Nomenclature 1 Product advantages 2 Product Features 2 Warnings 3 About Your Electric Tankless Water Heater 3 Before You Install Your Tankless Water Heater 4 Selecting Installation Location 4 Mounting Your Electric Tankless Water Heater 4 Dimensions 5 Installation Guideline 6 P...

Page 3: ...oes not require pre heating and there are not stand by heating losses 2 Reliable and safe water is completely separated from electricity by multi layers of composite nano insulation material 3 Advance micro processor control self diagnostic function automatically monitors and displays working conditions with soft start function providing constant temperature water flow by engaging heating elements...

Page 4: ...d to install a drip pan connected to a safe drain as per code requirements below the water heater to avoid property damage in case of eventual leaks and or install an active water leak detector and shut off valve to turn off your water supply in the event that a leak is ever detected Installation of this product is restricted to indoor locations only 2 ABOUT YOUR ELECTRIC TANKLESS WATER HEATER Ple...

Page 5: ...thawed out and you have inspected the unit for leaks It is recommended and you should give consideration to your existing plumbing configuration and location of your main electrical panel and future servicing DO NOT locate the unit in a location that will be difficult to access Most of the times it is better and easier to install your new appliance at the same location as your old one Combustible ...

Page 6: ...7 15 1x10 2x3 7 15 1x10 2x3 7 15 1x10 2x3 7 15 1x10 2x3 7 A x B x C MS120C2T_U MS150C2T_U MS180C2T_U MS210C2T_U MS240C2T_U MS270C2T_U in D x E x F MS150C2TMU MS180C2TMU MS210C2TMU MS240C2TMU MS270C2TMU 16 1 x 11 x 3 5 16 1 x 11 x 3 5 16 1 x 11 x 3 5 16 1 x 11 x 3 5 16 1 x 11 x 3 5 Injected Mold Model Stainless Steel Model ...

Page 7: ... C2TMU Stainless Steel Model Injected Mold Model Remove screw which fixes the bracket on back of the appilance Typical Remove the bracket from the appilance Typical Front and back of the appliance Typical Installation Guideline ...

Page 8: ...d simply set the front cover aside and keep the cable connected Fig 6 Fig 7 Hold the back bracket hanger in position against the wall and mark the three mounting holes Drill holes of inch 6 00mm diameter the distance between every two holes is 3 15 16 100mm Insert plastic anchoring in the hole place the bracket on the wall and secure the hanger using the screws supplied or an appropiate alternativ...

Page 9: ...tem 3 Install air vent valves expansion tanks flow control valves isolation valves etc as per code requirements 4 The unit is designed to operate only when flow sensor senses water flow through it Prior to powering up turning on your unit PURGE ALL AIR FROM YOUR SYSTEM see item 10 below failure to do so might cause an air lock in your unit drying out the heat exchanger of your unit and cause perma...

Page 10: ... 3 4 gpm 3 3 gpm 2 9 gpm 2 8 gpm 2 6 gpm 2 3 gpm 2 0 gpm 5 4 gpm 4 8 gpm 4 1 gpm 3 8 gpm 3 5 gpm 3 0 gpm 2 8gpm 2 5 gpm 2 4 gpm Inlet Water Temp 6 0 gpm 5 2 gpm 4 5 gpm 3 8 gpm 3 7 gpm 3 2 gpm 3 0 gpm 2 7 gpm 2 5 gpm 6 8 gpm 5 7 gpm 5 1 gpm 4 4 gpm 3 9 gpm 3 6 gpm 3 3 gpm 3 0 gpm 2 7 gpm Shower 1 5 gpm Sink Faucet 1 0 gpm All data above are based on water leaving temperature 105º F 40º C 1 5 gpm s...

Page 11: ... 19 22 26 30 34 6 0 14 17 20 24 27 31 6 5 13 16 19 22 25 28 7 0 12 15 18 20 23 26 27 Power kw Water Flow GPM 12 15 18 21 24 Temperature Rise o F Table 2 Temperature Rise o F 240V vs Flow Rate GPM 0 10 20 30 40 50 60 70 80 90 100 110 120 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 Flow Rate GPM MS120C2T MS150C2T MS180C2T MS210C2T MS240C2T MS270C2T Temp Rise o F Flow Rate gpm kW rating x...

Page 12: ...ouse has sufficient electrical power available to handle the maximum amperage load of the applicable model of your heater A Make sure all power sources to the unit are disconnected before doing any connection to the terminal box and working with it Follow the wiring diagrams based on the unit you have purchased All mounting and plumbing installation must be completed before proceeding with the ele...

Page 13: ...ET TEMP SENSOR FLOWMETER OUTLET TEMP SENSOR THERMAL CUT OUT 194º F E L1 L2 Display screen E G L1 L2 Double Pole Breaker 60 A MS120 WIRE CONNECTIONS TO BREAKERS 11 22 in Display screen UP ON OFF DOWN 10 2 in Bottom case Heating chamber Control board Terminal blocks Flowmeter Temp sensor Wiring Diagram Fig 10 Fig 11 ...

Page 14: ... 50 A MS180 Double Pole Breaker 40 A MS150 50 A MS180 16 14 in 11 in 13 MS150C2T_U MS180C2T_U THERMAL CUT OUT 194º F REMARK J RELAY R HEATING SYSTEM T TRIAC L1 L1 T1 T2 R1 R2 L2 E CONTROL SYSTEM DISPLAY SCREEN INLET TEMP SENSOR FLOWMETER OUTLET TEMP SENSOR L2 B 2 MS150C2T_U MS180C2T_U must be connected to two double pole breaker Read all name plates carefully and wire as per instructions and table...

Page 15: ...n Terminal blocks Flowmeter Temp sensor Heating chamber Display screen UP ON OFF DOWN WIRE CONNECTIONS TO BREAKERS E G L1 L2 L1 L2 L1 L2 Double Pole Breaker 40 A MS210 40 A MS240 50 A MS270 Double Pole Breaker 40 A MS210 40 A MS240 50 A MS270 Double Pole Breaker 40 A MS210 40 A MS240 50 A MS270 11 in 16 14 in B 3 MS210C2T_U MS240C2T_U MS270C2T_U must be connected to three double pole breaker Read ...

Page 16: ...4 3 2 Working pressure PSI bar Max 150 10 Weight lb 17 6 Product Dimensions in 16 1 x 11 x 3 5 Water connections NPT 3 4 3 4 3 4 3 4 3 4 17 6 17 6 17 6 17 6 16 1 x 11 x 3 5 16 1 x 11 x 3 5 16 1 x 11 x 3 5 16 1 x 11 x 3 5 Check your local electrical code requirements for different voltage application Model MS120C2T_U MS150C2T_U MS180C2T_U MS210C2T_U MS240C2T_U MS270C2T_U Phase 1 1 1 1 1 1 Voltage V...

Page 17: ...pplied with power a beep sound can be heard and LED lights for 2 seconds no other display the appliance keeps standby 5 Press to turn ON OFF the appliance When the unit is ON LED displays actual temperature of the outlet water After 5 seconds the screen switches to the screen saver to conserve power The display screen light will be off If you touch the screen it will light up again 6 The outlet wa...

Page 18: ...lean strainer and shower 7 LED displays E1 Outlet temp is over 67 153 A Reduce the temperature B Turn up the water flow 8 LED displays E3 Temperature sensor failure Please contact with your local dealer 9 Display overload Inlet water flow is too high Reduce the inlet water flow 10 LED Displays E4 Dry heating Shut off Clean all outlets of any debris dirt any particle or scale inside the pipe 11 Pre...

Page 19: ...t 305 593 8358 for any questions you might have and warranty service or if your certified installer needs assistance when installing a unit Your valuable suggestions and comments are always welcome it will help us to continuously improve our service as part of our commitment to serve you better 305 593 8358 customerservice klimaire com www klimaire com 18 ...