ELECTRICAL CONNECTIONS 

 

All electrical connections are made on terminal block TB1.  Set power switch to match the voltage of the 
AC line,  
115 or 230vac.  Connect AC power to terminals 3 and 4.  Set the input jumpers JP1 and JP2 to the 
positions corresponding to the control input signal type.  For a 4 to 20 madc input, place the jumpers to 
connect JP1-1 with JP1-2 and JP2-1 with JP2-2. For 0-10vdc input, place jumpers to connect JP1-2 with 
JP1-3, and JP2-2 with JP2-3.  Connect the appropriate control input signal to terminals 1 and 2.  Terminal 
2 is the lower potential line. 

 

 
 
 
 
 
 

 
The IPT has been adjusted at the factory for a 4 to 20 madc or 0 to10 vdc control input signal to produce 
a 0 to 80 psig output pressure.  No further adjustments are required.  However, if adjustment of the output 
pressure is desired, see note below. 
 

SPECIFICATIONS 

 

Input Power ..................................................... 115/230 vac 

±

10%, 50/60 Hz, switch selectable 

Control Input...................................................  4 to 20 madc, 249

Ω

 input impedance 

 

 0 to 10 vdc, 10K

Ω

 input impedance 

Output Pressure .............................................  0 to 80 psig 
Maximum Supply Pressure ............................  150 psig 
Minimum Supply Pressure .............................  greater than maximum desired output pressure 
Linearity, Hysteresis & Repeatability .............  0.5% of full scale 

 

3

0 to 10V

JP1

4 to 20mA

JUMPERS SET FOR

0 TO 10vdc CONTROL INPUT

JP2

3

2

2

1

1