NOTE:

 ADJUSTMENT (Not normally required)

 

 

The adjustment procedure is as follows: 

1.  Adjust the control input signal to a level slightly greater than its minimum value (0vdc or 4ma). 

2.  Adjust the "offset" potentiometer until the output pressure is slightly greater than zero. 

3.  Adjust the control input signal to its maximum value. 

4.  Adjust the "gain" potentiometer until the output pressure is at the desired maximum level. 

5.  Repeat this procedure as required. 

 

 

 

 

 
 

 

 