COMMISSIONING
5 - 1
DSE-17
www.maxcess.eu
MI 1064 1 C
Inbetr
iebna
hme.fm
5 COMMISSIONING
WARNING
Unexpected movements of the machine may lead to injuries
or death.
Commissioning must only be performed while the machine is
stopped and protected against being turned on again.
Make certain there is no one in the hazardous area of the
drives.
Calibrating the sensor
inputs of the web guide
controller
When the DSE-17 sensor is connected to the web guide controller
for the first time, the selected sensor input of the web guide
controller must be calibrated to the output signals of the DSE-17.
This ensures that the web guide controller and sensor use the
same standard of evaluation.
This process must be performed for each of the up to four
signals of the sensor (for example the edge signal or dirt
contamination signal).
For the assignment of sensor signals to inputs of the web guide
controllers, see the configuration drawing for the DSE-17 in the
system documentation.
Note:
If no key is pressed for more than 2minutes the sensor returns
to its regular operation state.
Calibration
∙
Press S1 and hold it for 3seconds
LED H1 flashes (short on - long off)
Depending on the configuration, all analog outputs of the
sensor return 0mA or 4mA.
This assigned value is used to determine the reference value
for the uncovered sensor on the web guide controller (no
material in the field of view).