i-MAX
Industrial inverter air/water heat pump with axial fans
10
5.2.10
LED STATUS DESCRIPTION
Compressor LED
•
ON if the compressor is running
•
OFF if the compressor is off
•
FLASHING if timings are in progress waiting for compressor’s start up.
Sanitary water LED
•
ON if sanitary mode is fulfilled active
•
OFF if the sanitary mode is not active
•
FLASHING if the sanitary production is in progress (sanitary valve is active)
Defrosting LED
•
ON in defrost operating mode
•
OFF if defrosting mode is disabled or completed
•
FLASHING if defrosting cycle interval’s time counting is in progress.
Antifreeze electric heater LED
•
The LED is ON if the antifreeze electric heater is active.
Water pump LED
•
The LED is ON if the water pump is running.
Alarm LED
•
The LED is ON if an alarm is activated.
Heat LED
•
The LED is ON if the unit is in the heating mode operation.
Cool LED
•
LED is ON if the unit is in the cooling mode operation.
6
I/O PORTS OF THE SYSTEM
The configurable I/O ports are as follows:
Parameter Default
value
Value = Function
Terminals
Notes
H47
2
Remote on-off digital input
ID3
Voltage free contact input
*H81
0
21= Defrosting cycle signalization
24= Alarm signalization
31=Plant season signalization
47=Lockout signalization
DO3(phase)
DO3N(neutral) Under voltage output 230Vac, 50Hz, 2A (AC1).
(*) For the sizes of 0466, 0475 and 0485
Wherever the GI optional plant management kit is present, you have a third controller located inside the electrical board acting as
an expansion module of the I/O ports. By mean of this controller, it is therefore possible to increase the number of logic functions
that can be managed by the main controller; in particular, the following I/O ports can be activated by the previous controller.
Parameter
Default
value
Value = Function
Terminals
Notes
H57
0
0=Disenabled function
3=Selected mode
19=Thermostat
26=Double set point
28=Sanitary call
ID3E
Voltage free contact input
H28
0
6=DHW remote sensor
ST6E
NTC-
10kΏ at 25°C β 3435
H29
0
41=Plant circuit water remote sensor
ST7E
H86
0
21=Defrost cycle warning
DO1(phase)
DO1N(neutral)
Under voltage output 230Vac, 50Hz, 2A
(AC1).
H87
0
31=Plant season warning
DO2(phase)
DO2N(neutral)
H88
0
24=Alarm warning
47=Lockout warning
DO3(phase)
DO3N(neutral)
H89
0
6= Sanitary valve
DO4(phase)
DO4N(neutral)
H90
0
26= Double set-point valve
43= Secondary circulator
DO5(phase)
DO5N(neutral)
7
OPERATION’S LOGICS
The following operation logics are enabled by the master controller
CB
(
MASTER
), situated on the front panel of the unit.