i-MAX 

Industrial inverter air/water heat pump with axial fans 

28

 

The parameters can be activated and/or modified by the user or by entering the installer password in the controller that is located 

on the front panel of the unit. 

DESCRIPTION 

GROUP IDENTIFICATIVE CODE 

INDEX OF THE PARAMETER 

VISIBILITY 

Configuration 

CnF 

H- 

USER/INSTALLER 

Compressor 

CP 

C- 

INSTALLER 

Fan motor 

FAn 

F- 

INSTALLER 

Alarms 

ALL 

A- 

INSTALLER 

Regulation 

Re 

b- 

INSTALLER 

Pump 

PUP 

P- 

INSTALLER 

Electric heaters 

Fro 

r- 

INSTALLER 

Defrosting 

dFr 

d- 

INSTALLER 

Electronic valve 

EEu 

U- 

INSTALLER 

Offset 

OFF 

o- 

INSTALLER 

Inverter compressors 

nCP 

n- 

INSTALLER 

11.1

 

SETPOINT CONFIGURATION PARAMETERS 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations 

Notes 

Coo 

First setpoint in cooling 

°C 

7.0 

H03÷Co2 

USER 

 

 

Hea 

First setpoint in heating 

°C 

45.0 

He2÷H01 

USER 

 

 

San 

DHW (sanitary) setpoint 

°C 

48.0 

H02÷H01 

USER 

 

 

Co2 

Second setpoint in cooling 

°C 

18.0 

Coo÷H03 

USER 

 

 

He2 

second setpoint in heating 

°C 

35.0 

H02÷Hea  

USER 

 

 

11.2

 

CONFIGURATION PARAMETERS

 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations 

Notes 

H01 

Maximum set point in heating 

°C 

63.0 

-50.0÷80.0 

INSTALLER 

 

 

H02 

Minimum set point in  heating 

°C 

25.0 

-50.0÷80.0 

INSTALLER 

 

 

H03 

Maximum set point in cooling 

°C 

25.0 

-50.0÷80.0 

INSTALLER 

 

 

H04 

Minimum set point in cooling 

°C 

5.0 

-50.0÷80.0 

INSTALLER 

 

 

H47 

Configuration of digital input ID3 

0÷30 

INSTALLER 

0 = input not assigned 

21=On/Off 

ID3, ID3 terminals

 

H126 

Serial address 

1÷200 

INSTALLER 

In case of several units installed in cascade 

configuration, you have to assign different 

addresses for each controller. 

 

11.3

 

ALARM CONFIGURATION PARAMETERS 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations

 

Note 

A08 

Antifreeze alarm activation setting 

°C 

-127÷127 

INSTALLER 

 

 

A09 

Antifreeze alarm hysteresis 

°C 

3.0 

0.0÷25.5 

INSTALLER 

 

 

A16 

Low pressure set in cooling operation 

Bar 

Based on the model  4,0÷80,0 

INSTALLER 

 

 

A27 

Low pressure set in heating operation 

1.3 

0.0÷25.5 

INSTALLER 

 

 

11.4

 

SETTING PARAMETERS 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations

 

Note 

b01 

Band in cooling mode 

°C 

2,0 

0÷10,0 

INSTALLER   

 

b02 

Band in heating mode 

°C 

2,0 

0÷10,0 

INSTALLER   

 

b03 

Differential in DHW mode 

°C 

4,0 

0÷10,0 

INSTALLER   

 

b04 

Radiant panels valve communication time 

sec 

30 

0÷600 

INSTALLER   

 

b05 

Hysteresis cut-off of the compressor in cooling and 

heating operation 

°C 

0.5 

0.0÷25.5 

INSTALLER 

Recommended values included 

between 1 and 1.5 

Other different values can ensure 

the proper operation of the unit 

 

b06 

DHW transitory output in heating 

sec 

45 

0÷255 

INSTALLER   

 

b07 

PI regulator integral time 

sec 

Based on 

the model 

0÷255 

INSTALLER 

It is recommended to set 60 sec for 

systems with limited water flow, and 

180 sec for systems with high water 

flow. Other values can ensure the 

optimal operation of unit. 

 

b08 

Enabling dynamic set 

0÷1 

INSTALLER   

 

b09 

Max Offset in cooling dynamic set 

°C 

3.0 

-50.0÷80.0  INSTALLER   

 

b10 

Max Offset in heating dynamic set 

°C 

-3.0 

-50.0÷80.0  INSTALLER   

 

b11 

Outdoor set temperature in cooling dynamic set 

°C 

25 

-127÷127  INSTALLER   

 

b12 

Outdoor set temperature in heating dynamic set 

°C 

15 

-127÷127  INSTALLER   

 

b13 

ΔT in cooling

 

°C 

-10.0 

-50.0÷80.0  INSTALLER   

 

b14 

ΔT 

in heating 

°C 

10.0 

-50.0÷80.0  INSTALLER   

 

b15 

Setpoint regulation band from 0-10V analog input 

°C 

5.0 

0.0÷10.0 

INSTALLER   

 

b16 

Scan time of compressors start-up 

sec 

60 

0÷255 

INSTALLER   

 

b19 

Minimum duration of the modulating compressor 

capacity for grade increase 

sec 

Based on 

the model 

0÷255 

INSTALLER   

 

b20 

Enabling of 0-10V/ratiometric input 

0÷1 

INSTALLER  0 = 0-10V input 

1 = ratiometric input 

 

b22 

Thermoregulation Hysteresis cut-off plant sensor 

°C 

1,5 

0.0÷25.5 

INSTALLER   

 

Summary of Contents for i-MAX 0466

Page 1: ......

Page 2: ...e Series Serie Serie S rie i MAX SSL 0466 06115 Industrial inverter air water heat pump with axial fans Possible wasted electrical or electronic devices products should not be located together with no...

Page 3: ...12 7 2 3 OPERATION WITH ACTIVE ELECTRIC HEATER 12 7 2 4 CONTINUOUS OPERATION 12 7 2 5 LINEAR REGULATION OF THE CIRCULATOR DOUBLE TWater 12 7 2 6 AIR PURGING OF THE SYSTEM 13 7 3 COMPRESSORS CONTROL 1...

Page 4: ...9 10 6 AUXILIARY SYSTEMS OFFSET MANAGEMENT 26 9 11 DOUBLE SET POINT MANAGEMENT 26 9 11 1 SETTINGS 26 9 11 2 ADJUSTABLE SETPOINTS 27 9 11 3 COMMUTATIONS 27 9 12 SECONDARY CIRCULATOR MANAGEMENT RELAUNC...

Page 5: ...personnel and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectl...

Page 6: ...nt under voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a...

Page 7: ...djust the summer set point value UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In t...

Page 8: ...cond setpoint in the summer C 18 0 Coo H03 He2 Second setpoint in the winter C 35 0 H02 Hea 5 2 2 Password menu Enter the password for the desired access level The controller will automatically open t...

Page 9: ...sequence 6 Once the update is completed the board returns to normal operation and the appliance is ready to start operation 7 Turn off the unit by placing the main switch in OFF position 8 Remove the...

Page 10: ...tion 24 Alarm signalization 31 Plant season signalization 47 Lockout signalization DO3 phase DO3N neutral Under voltage output 230Vac 50Hz 2A AC1 For the sizes of 0466 0475 and 0485 Wherever the GI op...

Page 11: ...n Continuous operation The circulator will immediately switch off if You have a pump circulator locking alarm including the manual reset flow switch alarm The unit is in stand by mode or when it s swi...

Page 12: ...it will be activated periodically for a duration given by the parameter P17 in seconds after a counting time set by the parameter P16 in minutes activated when the thermoregulation is fulfilled and th...

Page 13: ...the expansion valve the reversing valve is commutated in the opposite direction to that required by the actual mode for 5 seconds in order to allow the equilibrium of the optimal pressures for startin...

Page 14: ...15 b05 C 0 5 0 5 0 5 0 5 0 5 0 5 b25 C 2 5 2 5 2 5 2 0 2 0 2 0 7 3 5 INVERTER COMPRESSORS CONTROL IN HEATING MODE The compressors are active in heating mode if the heat pump is enabled H09 Configurati...

Page 15: ...ee the paragraph related to auxiliary electric heaters 7 5 HEAT DISSIPATION FAN MOTOR CONTROL The control of the dissipation is as a function of the condensing pressure in chiller mode operation where...

Page 16: ...rtant decreasing of the thermal efficiency of the unit it can lead also to the risk of damaging the unit itself The adjustable parameter d01 enables the defrost operation 1 enabled defrosting Please s...

Page 17: ...ated above on the DO3 DO3N terminals Parameter H81 it s possible to configure a 230Vac signal output voltage by setting the following user parameters introducing the installer password in the control...

Page 18: ...water production DHW 3 The function is active in heating mode The remote switching on off function doesn t deactivate the domestic hot water production DHW 4 The function is active in heating mode Th...

Page 19: ...hole system Note It is possible to invert the polarity of the digital input to do that please contact our technical office 9 5 3 HEATING MODE ON DOMESTIC HOT WATER TANK If the following setting H83 1...

Page 20: ...eater r24 Num 1 o 3 Type of utilization of the electric heaters 9 8 2 AUXILIARY ELECTRIC HEATER OF THE PLANT IN DEFROST CYCLE During defrost cycle see Paragraph 7 6 by setting r21 1 in addition to r10...

Page 21: ...h DHW and plant sides no priority intervention for electric heaters Settings of the parameter r32 when the boiler is being installed r32 0 boiler without a circulating pump with thermoregulation to be...

Page 22: ...his remote sensor is less than the setpoint Hea the boiler will be activated and then will be deactivated when the measured temperature by the remote sensor is greater than setpoint Hea The boiler wil...

Page 23: ...0 1 0 1 2 2 3 5 6 0 1 7 1 Auxiliary electric heater of sanitary 2 After r15 minutes boiler HEAT SAN SANITARY 0 1 1 Set up of minutes 2 3 2 3 8 1 Boiler 2 After r15 minutes auxiliary electric heater o...

Page 24: ...ter r12 minutes later heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set up of minutes 1 3 1 3 3 1 Boiler 2 After r12 minutes heat pump 3 After r12 minutes later auxiliary electric heater of plant HEAT HEAT SAN...

Page 25: ...AN HEAT 0 1 0 1 2 Set up of minutes 1 3 4 6 0 2 8 1 Auxiliary electric heater of plant HEAT HEAT SAN HEAT 0 1 0 1 2 Set up of minutes 0 2 5 1 3 9 1 Boiler HEAT SAN SANITARY 0 1 0 1 2 Set up of minutes...

Page 26: ...to the open state the auxiliary electric heater of the plant will turned off It works as indicated in the TABLE 1 2 3 and 4 3 COOL SAN SANITARY Not available It works as indicated in the TABLE 5 4 COO...

Page 27: ...ng pump for the plant circuit utilizations An ambient thermostat must be appropriately configured NC state connected on the terminals DI3E DI3E by the installer Thermostat contact normally open Active...

Page 28: ...eeze alarm activation setting C 2 127 127 INSTALLER A09 Antifreeze alarm hysteresis C 3 0 0 0 25 5 INSTALLER A16 Low pressure set in cooling operation Bar Based on the model 4 0 80 0 INSTALLER A27 Low...

Page 29: ...periodic mode min 20 0 600 INSTALLER P17 Time of operation of the pump in periodic mode sec 90 0 255 INSTALLER 0 deactivation of periodic mode P18 Enabling of unique pump operation in network 0 0 1 I...

Page 30: ...activated function 1 enabled function 2 Operation of auxiliary plant side electric only if H83 1 r16 DHW auxiliary heater heat pump activation delay min 15 0 255 INSTALLER r19 Activation time of drain...

Page 31: ...matically reset for the first 2 times and goes off after 5 seconds If the alarm occurs more than 3 times per hour the manual reset of the alarm is required The alarm is not active for 10 seconds after...

Page 32: ...pump E041 Misfitted temperature alarm Heat pump E101 Communication Timeout GI module error Heat pump E611 Inlet water temp sensor error Heat pump E682 Plant water plant temperature remote sensor if e...

Page 33: ...1 E913 Automatic All compressors are off for at least 180 sec E921 E923 Automatic All compressors are off for at least 180 sec E931 E933 Automatic All compressors are off for at least 180 sec E941 E94...