i-MAX
Industrial inverter air/water heat pump with axial fans
30
H57
Configuration of the digital input
ID3E
/
0
0÷26
INSTALLER
0 = Function not active
3 = Remote selection for Summer/Winter mode
19= Secondary circulator thermostat
26 = Double set point
28 = Sanitary mode call
ID3E, ID3E terminals
H129
Enablement of double setpoint
/
0
0÷1
INSTALLER
0 = Function not active
1 = Classic mode
2= Summer double setpoint
3= Winter double setpoint
4 = Summer and winter double setpoint
CONFIGURATION PARAMETERS OF THE HEATING DEVICES
Parameter
Description
Unit
Default
Range
Visibility
Allowed configuration
Note
r02
Setpoint of anti-freeze heater in
heating mode
°C
3
3÷6
INSTALLER
r03
Setpoint of anti-freeze heater in
cooling mode
°C
3
3÷6
INSTALLER
r06
Differential of anti-freeze
electric heater
°C
2.0
0.0÷25.5
INSTALLER
r08
Upper limit during in
substitution operation
°C according to
the model
-16÷50
INSTALLER
Respect the condition
r22
≥
r28
≥
r08
r09
Hysteresis for heat pump
lockout
°C
1.0
0.0÷25.5
INSTALLER
r10
Enabling the auxiliary electric
heater of the plant
/
0
0÷1
INSTALLER
0 = deactivated function
1 = enabled function
r11
Differential of the plant auxiliary
electric heater
°C
0.5
0.0÷25.5
INSTALLER
r12
Auxiliary plant/HP electric
heater activation delay
min
10
0÷255
INSTALLER
r13
Auxiliary heater deactivation
delay
min
10
0÷255
INSTALLER
r14
Exclusive operation of the
electric-heaters
/
0
0÷1
INSTALLER
0 = Simultaneous enabling of the electric heaters
1 = Exclusive enablement of the electric heaters
r15
DHW auxiliary electric heater
enablement
/
0
0÷2
INSTALLER
0 = deactivated function
1 = enabled function
2 = Operation of auxiliary plant-side electric
only if H83=1
r16
DHW auxiliary heater/heat pump
activation delay
min
15
0÷255
INSTALLER
r19
Activation time of drain pan
heaters from last defrost
min
0
0÷255
INSTALLER
0= activation of E-heater independently of
defrosting.
r20
E-heater priority utilization
/
1
0÷1
INSTALLER
0 = priority for plant-side
1 = priority for DHW side
Only if r14 = 1
r21
Plant side mitigation enabling
with heaters in defrost
/
0
0÷1
INSTALLER
0 = deactivated function
1 = enabled function
r22
Upper limit joint operation area I
°C according to
the model -127÷127
INSTALLER
Respect the condition
r22
≥
r28
≥
r08
r23
Type of boiler utilization
/
60
0÷6
INSTALLER
r24
Type of use of the auxiliary
heaters
/
3
0÷3
INSTALLER
r25
Disinfection Setpoint (anti-
legionella)
°C
80
0÷100
INSTALLER
Adjustable parameters
by mean of remote
control panel
Hi-T
r26
Disinfection period
min
12
0÷255
INSTALLER
Adjustable parameters
by mean of remote
control panel
Hi-T
r27
Heat pump set in disinfection
operation
°C
55.0
-50.0÷80.0
INSTALLER
Adjustable parameters
by mean of remote
control panel
Hi-T
r28
Upper limit for joint operation
area II
°C according to
the model
-16÷50
INSTALLER
Respect the condition
r22
≥
r28
≥
r08
r29
Temperature offset for boiler
and plant according to the
setpoint (G02)
°C
0
0÷100
INSTALLER
r30
Temperature offset for boiler
and plant according to the
setpoint (G05)
°C
0
0÷100
INSTALLER
r31
Temperature offset for boiler
and DHW electric heaters (G03)
°C
0
0÷100
INSTALLER
r32
Boiler endowment
/
1
0÷3
INSTALLER
r33
Pump management with
electric heaters ON
/
3
0÷4
INSTALLER
12
WATER WITH GLYCOL
For the models where the water with glycol is required, please contact the company offices for the necessary modifications.