Hi-T2
Centralised controller
41
8
FAN COIL CONFIGURATION PARAMETERS
NB: Please make reference to the manual of RFC controls for more details about the parameterization and the operation of the
product. (MCO01137I0300).
The service parameters of the fan coil units which can be modified by Hi-T2 control panel are described in the following table:
N.
PARAMETER NAME
MINIMUM
VALUE
MAXIMUM
VALUE
VALUE
DEFAULT
UNIT
OF
MEASUREMENT
1
Setpoint limits
5 = Relative setpoint 0°C
6 = Relative se/-1°C
7 = Relative se/-2°C
8 = Relative se/-3°C
9 = Relative se/-4°C
10 = Relative se/-5°C
5
10
5
---
2
Neutral band
0 = Neutral band 4.0°C
1 = Neutral band 3.0°C
2 = Neutral band 2.0°C
3 = Neutral band 1.0°C
4 = Neutral band 0°C
0
4
2
---
3
Plant type
0 = 2-PIPE plant
1 = 4-PIPE plant
0
1
0
---
4
Fan mode
0 = CONTINUOUS FAN
1 = FAN ALWAYS THERMOSTAT CONTROLLED
2 = CONTINUOUS FAN ONLY IN SUMMER
3 = CONTINUOUS FAN ONLY IN WINTER
0
3
0
---
5
Actuator type
0 = ON-OFF ACTUATOR
0
0
0
---
6
Window contact type
0 = ACTIVE IN CLOSING
1 = ACTIVE IN OPENING
0
1
0
---
7
Reduction of eco setting
0 = 2°C
1 = 4 °C
2 = 6 °C
3 = 8 °C
4 = 10 °C
0
4
2
---
8
Water temperature probe function
2 = Fan consent in winter
3 = Water temperature probe not present
2
3
2
---
10 Temperature Offset
0 = Offset 0.0 °C
1 = 1.0 °C
2 = Offset - 1.0 °C
3 = 2.0 °C
4 = Offset - 2.0 °C
0
4
0
---
11 Primary electric heater fan motor speed
Sets the fan speed motor 0-10V with primary electric
heater
0.0
10.0
5.0
V