- 5 -
<How to install so that adhesion and accumulation of
transported materials is minimized>
Install as shown in Fig. 4, so that the transmitting and
receiving surface is flush with the container wall
(tube, pipeline, etc.).
If installation shown above is not possible, install a shield
made of a material such as low-permittivity Teflon or ceramics
to allow microwave transmission.
Important:
:
Do not use a shield made of an
electroconductive material.
It may cause a false detection, especially when
the measured material contains some moisture.
5. Flow Monitor Installation Conditions
5-1. Free-Fall Applications
Fig.4 Installation to Minimize Adhesion and
Accumulation of Transported Material
Fig.5 Installation on Free-Fall Equipment
Flow Monitor
Fall height (A)
300 mm or more
Metal piping
Same height as (A) or more
!
Important:Metal pipes must be used for the equipment piping.
Be sure to secure the required heights for installation.
!