Mass Sine Ultra
– Installation Manual Multiple Units
Three-phase configuration with MasterAdjust
15
9. Select
Installer
and enter the installer code.
10. Go to the Configuration tab and give the unit a logical name. For example, MSU L1, MSU L2 and MSU L3.
11. Return to the Configuration tab of the L1 unit. All settings are done here. However, if Mastervolt Lithium-Ion batteries are
connected, all events, like Stop Discharge for example, must be configured for ALL units separately.
12. In the
Cluster
pane, from the
Phase System
drop-down list, select
Three Phase
. You may need to maximize the
MasterAdjust window or scroll all the way to the right to see this.
13. From the
Dev. Per phase
drop-down list, select PER PHASE the number of units in parallel (P Replica)! In our
example this is 1.
14. Click the
Select devices
button to be able to select the L2 and L3 units.
In the
Phase L2
section, from the
Phase master
(Primary) drop-down list, select the L2 unit.
In the
Phase L3
section, from the
Phase master
(Primary) drop-down list, select the L3 unit.