14
15
model no. 299-1978-8 | contact us 1-800-689-9928
OPER
A
CAUTION!
Verify that the metal bars in the water tray are covered with water. The water pump may be
damaged if it is not completely submerged while the tile saw is in use.
OPERATING INSTRUCTIONS
Breaking-in the pump
1.
Set the pressure switch (C) to the OFF position.
2.
Open the tank drain valve (I) by turning it counterclockwise to permit the air to escape and
prevent air pressure build-up in the air tank during the break-in period.
3.
Turn the air pressure regulator (E) counterclockwise until it stops.
OFF
open
OPEN
4.
Plug in the power cord (K).
NOTE:
A circuit breaker is recommended. If the air compressor is connected to a circuit protected by a
dual-element time delay fuses (type “T” only).
5.
Set the pressure switch (C) to the ON position. The compressor will start. Run the compressor for 30
minutes. If it fails, turn it off immediately and call the toll-free helpline at: 1-800-689-9928. Please note
that breaking-in the unit is only required prior to first use.
6.
After 30 minutes, turn off the pressure switch (C).
7.
Close the tank drain valve (I) by turning it clockwise.
8.
Set the pressure switch (C) to the ON position
.
The air receiver will fill to “cut-out” pressure and then
the compressor’s motor will stop. The compressor is now ready for use.
CLOSE
ON
CAUTION!
Use a dedicated circuit.
For best performance and reliable starting, the air compressor should be plugged into a dedicated circuit,
as close as
possible to the fuse box or circuit breaker.
The compressor will use the full capacity of a typical 12
A household circuit. If any other electrical
from the compressor’s circuit, the air compressor may fail to start. Low voltage
sluggish starting that causes the motor overload protection
devices are drawing
or an overloaded circuit can result in
system or circuit breaker to trip, especially in cold conditions.
fuse, use
OPERATING INSTRUCTIONS