2
Combination Unit Positioning:
1. Place combination unit in desired position, far enough from walls
and other obstructions to allow for servicing the unit.
2. Place the combination unit within reasonable access to a
grounded 115V/60 HZ circuit and a legal drain line connection.
Combination Unit Tank Loading: NOTE: Anion resin is pre-loaded
in the bottom tank at factory.
1. Remove yellow caplug from top of tank. DO NOT CUT white riser
tube.
2. The top of the distributor pipe will be
5/8” above the top of the
tank.
3. Cover the top opening of the distributor pipe before filling the tank
with media.
Model
Gravel
Filter Media
MP-CSU-20T
N/A
½ CF C-800
MP-CSU-30T
N/A
1 CF C-800
MP-CSU-40T
25 lbs.
1 CF C-800
MP-CST-20T
N/A
½ CF C-800
MP-CST-30T
N/A
1 CF C-800
MP-CST-40T
25 lbs.
1 CF C-800
MP-CSN-20T
N/A
½ CF C-800
MP-CSN-30T
N/A
1 CF C-800
MP-CSN-40T
25 lbs.
1 CF C-800
4. Pour all C-800 media provided with the unit into the top of the
tank.
5. Remove the material used to cover the top opening of the
distributor pipe.
Control Valve:
1.
When facing the front of the MP-MCA timer, the inlet connection
is located on the right and the outlet connection is on the left.
The control valve's inlet and outlet connections are either 1
”
copper or PVC equipped with split ring and nut.