AM, EM, AQ, BA, ASW - IOM
page: 53/64
Ing.Ji
ř
í Jiránek
heating system inlet/outlet
tap water inlet / DHW outlet
3 way valve
indirect DHW tank
heat exchanger
2-3m
2
/10kW !
AQ
5.9.3 Charging pump for tank with heat exchanger
Universal scheme usable for all types of heat pumps. The Charge Pump draws heating water
from accumulation boiler of the heating system and heats DHW. Recommended heat transfer
area of the exchanger is 2m2/300l of the boiler volume. During preparation of DHW the control
system automatically cancels the equithermal control and sets the required value of heating
water to maximum.
tap water inlet / DWH outlet
charging pump
heat source outlet
indirect DHW tank
heat exchanger
2-3m
2
/10kW !
heating system buffer