Masport I7000 Installation Instructions Manual Download Page 8

 

Page | 8 

 

  Refer schematic diagrams shown on page 13 for required opening. 

 
 

Warm air outlet vents 

  2 x warm air vent must be connected to outer of zero clearance cabinet.  

  These two vents can vent out the warm air in the front, side, rear, other adjacent room or either 

combination of these. 

  The vents must be installed minimum 300mm below the ceiling level 

  If  the  warm  air  output  vents  are  installed  on  the  side  or  rear  face  of the  built-in  cavity,  there 

should not be combustible nogs or cladding material within 300mm distance from any part the 
vent.  

  Refer schematic diagrams shown on page 13 for required opening. 

 

Ducting  

  Two lengths of 150mm diameter, semi rigid aluminium duct are supplied along with the fire.  

  These  can  be expanded  up to  1500mm  length  and  are  enough for installing  warm air  output 

vent in the same room, above or near the burner. 

  If required please purchase additional ducting that can withstand temperatures up to 250 

0

 

Cladding material  

  Support  shelf  must  be  minimum  18  mm  thick  non-combustible  material  like  Promina  or 

equivalent. 

  For front, & side faces of built-in cavity, use minimum 9 mm thick non-combustible material like 

Promina or equivalent.  

  For front cladding, maximum 32mm thick non-combustible material can be used.    

  The thickness of front cladding will dictate the nailing/anchoring position of the fire into built-in 

cavity.  Read  carefully  section  5.3  for  positioning  and  anchoring  fire  inside  the  built-in  cavity 
depending upon thickness.       
 

Mantle shelf  

  Considering the modern aesthetic of this model, mantle shelf is not recommended for Inverell / 

I7000 burner. 

  In case mantle shelf is to be build, it must be made of non-combustible material. 

  Glen Dimplex do not recommend installing TV above the fire.  

 

Flue System   

  150mm Flue with Double casing, Zero Clearance Flue Kit GDFLU021M Or equivalent flue kit 

that is compliant to AS/NZS 2918:2001 

  Top  of  the  built-in  cavity  or  chimney  chase  must  be  ventilated  either,  using  300mm  dia 

additional casing or side vent at the top of cavity.  

  Do not connect the fireplace to a flue system servicing another appliance or an air distribution 

duct. 

 

Refer schematic diagrams shown on page 15. 

 
 
 

 

Summary of Contents for I7000

Page 1: ...FUTURE REFERENCE Manufactured in New Zealand by GLEN DIMPLEX NEW ZEALAND LIMITED P O Box 58473 Botany Manukau 2163 Ph 0800 666 2824 Fax 09 274 8472 Email sales glendimplex co nz Web www glendimplex co...

Page 2: ...PECIFICATIONS 5 3 0 WORKING PRINCIPLE OF INVERELL I7000 6 4 0 LOCATION OTHER IMPORTANT CONSIDERATIONS 7 5 0 INSTALLATION PROCEDURE FOR INVERELL I7000 9 5 1 BUILT IN FRAMING 9 5 1 1 MINIMUM CLEARANCES...

Page 3: ...s are heavy and tall in size with a total weight of 190 kg Single person handling could cause injury hence Masport recommends suitable handling equipment or two persons while handling both outside and...

Page 4: ...action is considered the manufacturer should be consulted in the first instance Inverell I7000 burner and flue system must be serviced at least once a year or more frequently depending upon usage 1 5...

Page 5: ...along with the flexible ducting fitted to its outer casing The ducting is then vented into the living room or adjacent room In both Australia and New Zealand Inverell I7000 has been tested to and com...

Page 6: ...es around this superhot firebox absorbs heat energy from its outer surfaces and becomes hot to a significant level This hot air rises and exist the zero clearance cabinet through two circular ports lo...

Page 7: ...stalled at an elevated height floor protector requirement depends upon the elevation of fire above ground Support shelf can be maximum up to height of 670mm above the ground Floor protector For an ele...

Page 8: ...be minimum 18 mm thick non combustible material like Promina or equivalent For front side faces of built in cavity use minimum 9 mm thick non combustible material like Promina or equivalent For front...

Page 9: ...5 0 Installation Procedure for Inverell I7000 burner 5 1 Built in Framing DO NOT FIX CLADDING UNTILL FIRE DUCTINGS AND VENTS ARE FULLY INSTALLED Page 9...

Page 10: ...5 1 1 Minimum clearances of built in enclosure to combustibles Page 10...

Page 11: ...by lifting and tilting from the hinge block Keep it away in safe place Take out carton box and keep its contents in safe place Take out 2 x semi rigid Aluminium ducts Remove 4x taptite screws two on...

Page 12: ...lize the entire fire horizontally within the built in cavity Simultaneously using piece of non combustible front cladding material as a gauge position the flanges of fascia forward out of cavity face...

Page 13: ...utout on front side and rear of the built in cavity for air inlets and outlets Air inlet holes need to be minimum 26000 mm2 open area each on side and rear of cavity approx 50mm above support shelf Us...

Page 14: ...ng front or side of the cavity Place the template on the front cladding mark and cut required cutout Use 2x self tapping screw and attach template to front cladding on two sides Drill four dia 4 5 top...

Page 15: ...ed by flue manufacturer Top of the built in cavity or chimney chase must be ventilated either using 300mm dia additional casing or side vent at the top of cavity To begin fix the ZC flue kit adaptor u...

Page 16: ...5 7 Floor Protector Use diagram below to install required floor protection Page 16...

Page 17: ...ring handing and installation of the fire For operations maintenance trouble shooting and warranty terms use Owner s Manual supplied along with the fire Important For any installation variations other...

Reviews: