Model: PM-2160-A
Doc. Ref. no. : m20Aom201
Issue no. 02
User’s Manual
Page 30 of 36
Function Code
= 0X06
Address
– Any Single Register between 40101 to 40130
Data
= Data of 1 word, as all data are of 2 Bytes [Decimal].
Response
= [0 x Slave Id], [0 x Fun. Code], [0 x ADD. High], [0 x ADD. Low], [0 x Data High],
[0 x Data Low], [0 x CRC Low] [0 x CRC High]
[Data Format:
only in Decimal
]
S. No. Address
Measured parameter
words
Minimum
value
Maximum
value
1
40101
Password
1
1
9999
2
40102
Slave address
1
1
247
3
40103
Baud rate (9600, 19200,
38400)
1
9600
38400
4
40104
*
1
Energy type
1
0
9
5
40105
System type (0
– 3P4W, 1 –
3P3W)
1
0
1
6
40106
PF1 type (read only value)
1
0
2
7
40107
PF2
type
(read
only
value)(For 3P4W only)
1
0
2
8
40108
PF3 type (read only value)
1
0
2
9
40109
Total PF type(read only value)
1
0
2
10
40110
*
2
CT Ratio
– High byte
1
11
40111
*
2
CT Ratio
– low byte
1
12
40112
*
2
PT Ratio
– high byte
1
13
40113
*
2
PT Ratio
– low byte
1
14
40114
Rated Voltage
(64,110,120,240)
1
64
240
15
40115
Rated Current (1,5)
1
1
5
16
40116
Pulse constant (KWH)*
3
1
100
60000
17
40121
Data type
(0-Real,1-Long)
1
0
1
18
40122
Demand Type
(0-KW, 1-KVA)
1
0
1
19
40123
Demand Method
(0-BLOCK, 1-SLIDE)
1
0
1
20
40124
Interval Time
1
15
30
21
40125
Sub Interval Time*
4
1
1
10
22
40126
Real Sec& Min [SSMM]
1
0
5959
23
40127
Real Hour & Date [HHDD]
1
1
2331
24
40128
Real Month & Year[MMYY]
1
100
1299
25
40129
Reset Individual Reg.*
5
(Write only)
1
77
84
26
40130
Reset all (Write only) *
6
1
85
85
Notes
*
1
Energy type has ten options 0
– KWH Import
1
– KWH Export
2
– KVARH – Import
3
– KVARH – Export
4
– KVAH
5
– MWH Import
6
– MWH Export
7
– MVARH – Import
8
– MVARH – Export
9
– MVAH