Model: PM-2160-A 

 

 

Doc. Ref. no. : m20Aom201 
Issue no. 02 
 

 
User’s Manual                                                                                                               

Page 28 of 36 

30202 

5th VrHar 

0.01 

30204 

7th VrHar 

0.01 

30206 

9th VrHar 

0.01 

30208 

11th VrHar 

0.01 

30210 

13th VrHar 

0.01 

30212 

15th VrHar 

0.01 

30214 

 Total Vrthd 

0.01 

30216 

Reserved  

   - 

10 

30218 

Reserved  

   - 

11 

30220 

Reserved  

   - 

12 

30222 

Reserved  

   - 

13 

30224 

Reserved  

   - 

14 

30226 

Reserved  

   - 

15 

30228 

Reserved  

   - 

16 

30230 

Reserved  

   - 

17 

30232 

3rd VbHar 

0.01 

18 

30234 

5th VbHar 

0.01 

19 

30236 

7th VbHar 

0.01 

20 

30238 

9th VbHar 

0.01 

21 

30240 

11th VbHar 

0.01 

22 

30242 

13th VbHar 

0.01 

23 

30244 

15th VbHar 

0.01 

24 

30246 

Total Vbthd 

0.01 

25 

30248 

3rd IrHar 

0.01 

26 

30250 

5th IrHar 

0.01 

27 

30252 

7th IrHar 

0.01 

28 

30254 

9th IrHar 

0.01 

29 

30256 

11th IrHar 

0.01 

30 

30258 

13th IrHar 

0.01 

31 

30260 

15th IrHar 

0.01 

32 

30262 

 Total Irthd 

0.01 

33 

30264 

Reserved  

   - 

34 

30266 

Reserved  

   - 

35 

30268 

Reserved  

   - 

36 

30270 

Reserved  

   - 

37 

30272 

Reserved  

   - 

38 

30274 

Reserved  

   - 

39 

30276 

Reserved  

   - 

40 

30278 

Reserved  

   - 

41 

30280 

3rd IbHar 

0.01 

42 

30282 

5th IbHar 

0.01 

43 

30284 

7th IbHar 

0.01 

44 

30286 

9th IbHar 

0.01 

45 

30288 

11th IbHar 

0.01 

46 

30290 

13th IbHar 

0.01 

47 

30292 

15th IbHar 

0.01 

48 

30294 

 Total Ibthd 

0.01 

          

ON Hour / LOAD Hour / IDLE Hour / Power Interruption Count:

          

 

Function Code

 = 0X04  

           

Address

 

– between 30301 to 30311 

           

No. of data word

 

≤ 11 & in multiple of 1 as all data are of 2 Bytes [Decimal].  

Summary of Contents for PM2160-A

Page 1: ...B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 79 91 79 23287281 82 Email support masibus com Web www masibus com User s Manual M MU UL LT TI IF FU UN NC CT TI...

Page 2: ...el Picture 12 3 2 Rear Panel Picture 13 4 TERMINAL CONNECTIONS 14 4 1 Rear Panel Terminal Connections 14 5 MECHANICAL GUIDELINE 15 5 1 Front Bezel Diagram 15 5 2 Panel Cutout Diagram 15 6 INSTALLATION...

Page 3: ...no m20Aom201 Issue no 02 Page 3 of 36 User s Manual Display Details for Run Mode and Configuration Mode 36 1 Annexure A2 Display Details for LED based PM2160 A 36 2 Annexure A3 Display Details for LCD...

Page 4: ...hout notice as a result of continuous improvements to the instrument s performance and functions This manual describes the functions of this product MASIBUS does not guarantee the application of these...

Page 5: ...eature even after Power On Off Light weight Rugged Reliable Safe for User Aux powered uses Switch mode power supply 4 lines 4 digit high visibility LED display 0 4 10mm to display various parameters O...

Page 6: ...manual 1 Safety Precautions The product and the instruction manual describe important information to prevent possible harm to users and damage to the property and to use the product safely Understand...

Page 7: ...D 4 line 4 digit 0 4 10mm 7 segment Display 3 line 4 digit in Red 1 line 4 digit in Green 3mm Round LED for Parameter Indication Bar type LED for indication Load LCD Panel Large multi line backlit LCD...

Page 8: ...2 of FS 0 5 of reading 0 02 of FS 1 0 of reading 0 02 of FS Active Energy Class 0 2s as per IS14697 IEC 62053 22 Class 0 5s as per IS14697 IEC 62053 22 Class 1 0 as per IS13779 IEC 62053 21 Reactive E...

Page 9: ...M 100KWh X XXX G 1MWh XX XX G 10MWh XXX X G 100MWh Sys Energy Resolution Display Format Unit Last Digit Resolution X XXXXX K 0 01Wh XX XXXXX K 0 01Wh XXX XXXXX K 0 1Wh X XXXXXXX M 1Wh XX XXXXXX M 1Wh...

Page 10: ...K 0 01Wh XXX XXXX K 0 1Wh X XXXXXX M 1Wh XX XXXXX M 10Wh XXX XXXX M 100Wh X XXXXXX G 1KWh XX XXXXX G 10KWh XXX XXXX G 100KWh Sys Energy Resolution Display Format Unit Last Digit Resolution X XXXXX K 0...

Page 11: ...emand with Date Time Rising Demand Harmonics THD Harmonics Up to 15th Odd C Hour ON Hour Load Hour RUN Hour Total Idle Hour C Load Hour RUN Hour Import Load Hour RUN Hour Export Power Interruption Pow...

Page 12: ...even Segment LED Display For LCD Panel Display Fig 3 1 Detail of front panel PGM ENT key RUN mode Key press is used to enter into PGM mode view mode PGM mode On key press If in view mode goes into edi...

Page 13: ...in edit mode used to shift to the next digit UP INCREMENT key RUN mode Key press is used to move from one frame to the other vertically up PGM mode Increment value in edit mode Move UP to next configu...

Page 14: ...2 RS 485 B 3 IB Current In B Phase Three Phase Current Inputs 4 IB Current Out B Phase 5 IY Current In Y Phase 6 IY Current Out Y Phase 7 IR Current In R Phase 8 IR Current Out R Phase 9 L Line Aux Po...

Page 15: ...Model PM 2160 A Doc Ref no m20Aom201 Issue no 02 Page 15 of 36 User s Manual 5 MECHANICAL GUIDELINE 5 1 Front Bezel Diagram 5 2 Panel Cutout Diagram All Dimensions are in mm...

Page 16: ...he instrument to the power source check the labels on the instrument to ensure that your instrument is equipped with the appropriate power supply voltage input voltages and currents Failure to do so m...

Page 17: ...as excessive shock vibration dirt moisture corrosive gases or rain The ambient temperature of the areas should not exceed the maximum rating specified 6 2 Common Wiring with RS 485 Connections Recomm...

Page 18: ...M 2160 A Doc Ref no m20Aom201 Issue no 02 User s Manual Page 18 of 36 6 3 1 Three Phase Four Wire System a 4 Wire Wye 3 Element Connection Using 3PTs 3CTs b 4 Wire Wye 3 Element Direct Connection Usin...

Page 19: ...Model PM 2160 A Doc Ref no m20Aom201 Issue no 02 Page 19 of 36 User s Manual c 4 Wire Direct Connection 6 3 2 Three Phase Three Wire System a 3 Wire 2 Element Open Delta Connection Using 2PTs 2CTs...

Page 20: ...s Manual Page 20 of 36 b 3 Wire 2 Element Direct Connection Using 2CTs 6 3 3 Single Phase Two Wire Configuration Note For Single Phase Two Wire system should be 3P4W and Do not consider Average Voltag...

Page 21: ...poor accuracy and phase characteristics Ensure that the CT primary rating has been selected so that your normal load variation lies between 40 and 80 of its full scale If your CT is over rated say if...

Page 22: ...ple of 2 as all data are of 4 Bytes Long Real Enter only Even value data word length Response 0 x Slave Id 0 x Fun Code Byte count Data High Data Low Data High Data Low 0 x CRC Low 0 x CRC High Data F...

Page 23: ...7 3 Varh Export 2 0 1 45 30089 T Varh Export 2 0 1 46 30091 1 Vah 2 0 1 47 30093 2 Vah 2 0 1 48 30095 3 Vah 2 0 1 49 30097 T Vah 2 0 1 50 30099 Rising Demand 2 0 1 51 30101 Real Date 2 52 30103 Real T...

Page 24: ...01 14 30226 13th VyHar 2 0 01 15 30228 15th VyHar 2 0 01 16 30230 Total Vythd 2 0 01 17 30232 3rd VbHar 2 0 01 18 30234 5th VbHar 2 0 01 19 30236 7th VbHar 2 0 01 20 30238 9th VbHar 2 0 01 21 30240 1...

Page 25: ...of 2 as all data are of 4 Bytes Long Real Enter only Even value data word length Data Format long Real S No Address Measured parameter words Multiplication Factor if data type is long 1 30350 Power O...

Page 26: ...31 30061 Reserved 32 30063 3_2 Wh Import 2 0 1 33 30065 T Wh Import 2 0 1 34 30067 1_2 Wh Export 2 0 1 35 30069 Reserved 36 30071 3_2 Wh Export 2 0 1 37 30073 T Wh Export 2 0 1 38 30075 1_2 Varh Impor...

Page 27: ...1 11 32021 S Var S Var 2 1 12 32023 S VA S VA 2 1 13 32025 T Wh Import T Wh Import 2 0 1 14 32027 T Wh Export T Wh Export 2 0 1 15 32029 T Varh Import T Varh Import 2 0 1 16 32031 T Varh Export T Var...

Page 28: ...2 0 01 24 30246 Total Vbthd 2 0 01 25 30248 3rd IrHar 2 0 01 26 30250 5th IrHar 2 0 01 27 30252 7th IrHar 2 0 01 28 30254 9th IrHar 2 0 01 29 30256 11th IrHar 2 0 01 30 30258 13th IrHar 2 0 01 31 3026...

Page 29: ...us master Note Energy will be in Kilo for Real data type and for Long data type multiply with constant stated to get energy in Kilo unit Note Ignore address which are not mentioned in the memory map a...

Page 30: ...PF3 type read only value 1 0 2 9 40109 Total PF type read only value 1 0 2 10 40110 2 CT Ratio High byte 1 11 40111 2 CT Ratio low byte 1 12 40112 2 PT Ratio high byte 1 13 40113 2 PT Ratio low byte 1...

Page 31: ...four byte D687 at 40111 and higher four byte 0012 at 40110 addresses respectively PF type has three options 0 Unity 1 Lag 2 Lead NOTE MODBUS Time out 4 Sec or more 7 4 Exception Responses Exception re...

Page 32: ...ave address etc you have to use function code 03 Here the addressing allows up to Maximum 24 registers Words to be obtained at each request 7 4 2 Preset Single Register Function Code 06 Function 06 wi...

Page 33: ...D IDLE Display two quantity Hours and Minute Power Interruption Count Number of Supply Outages means the number of Auxiliary Supply interruptions If the meter Auxiliary Supply is from a UPS then the I...

Page 34: ...Secondary 1A Therefore select Irated 1A CTR 100A 1A 100 select in meter Energy consumed per hour will be 66kV X 100Amps 6600KVAHr Time to overflow in Hr 400GVAhr 6600KvaHr 60606 Hr Days 60606 24 2525...

Page 35: ...ed for Multifunction meter setup parameters CT and PT ratings System Type Incorrect voltage inputs Check Multifunction meter voltage input terminals to verify that adequate voltage is present Multifun...

Page 36: ...Ref no m20Aom201 Issue no 02 User s Manual Page 36 of 36 Display Details for Run Mode and Configuration Mode 1 Annexure A2 Display Details for LED based PM2160 A 2 Annexure A3 Display Details for LCD...

Reviews: