Model: PM-2160-A
Doc. Ref. no. : - m20Aom201
Issue no. 02
Page 25 of 36
User’s Manual
47
30292
15th IbHar
2
0.01
48
30294
Total Ibthd
2
0.01
ON Hour / LOAD Hour / IDLE Hour / Power Interruption Count:
Function Code
= 0X04
Address
– between 30301 to 30311
No. of data word
≤ 11 & in multiple of 1 as all data are of 2 Bytes [Decimal].
[Data Format:
Only in Decimal
]
S. No.
Address
Measured parameter
words
Multiplication Factor
(if data type is long)
1
30301
ON HOUR
1
-
2
30302
ON MIN
1
-
3
30303
LOAD HOUR
1
-
4
30304
LOAD MIN
1
-
5
30305
IDLE HOUR
1
-
6
30306
IDLE MIN
1
-
7
30307
PWR INTR. COUNT
1
-
8
30308
IMPORT RUN HOUR
1
-
9
30309
IMPORT RUN MIN
1
-
10
30310
EXPORT RUN HOUR
1
-
11
30311
EXPORT RUN MIN
1
-
Power ON/OFF Date & Time:
Function Code
= 0X04
Address
– between 30350 to 30356
No. of data word
≤ 8 & in multiple of 2 as all data are of 4 Bytes [Long & Real].
Enter only Even value (data word length).
[Data Format:
long & Real
]
S. No.
Address
Measured parameter
words
Multiplication Factor
(if data type is long)
1
30350
Power Off Date
2
-
2
30352
Power Off Time
2
-
3
30354
Power On Date
2
-
4
30356
Power On Time
2
-
7.2 Modbus Register Map for 3P3W Parameters
Data read Query
= [0 x Slave Id], [0 x Fun. Code], [0 x ADD. High], [0 x ADD. Low], [0 x No.
of data word, High], [0 x No. of data word. Low] [0 x CRC Low] [0 x CRC High]
Function Code
= 0X04
Address
– between 30001 to 30121
No. of data word
≤ 122 & in multiple of 2 as all data are of 4 Bytes [Long & Real].
Response
= [0 x Slave Id], [0 x Fun. Code
], [Byte count], [Data High], [Data Low] …... [Data.
High], [Data. Low] [0 x CRC Low] [0 x CRC High]
[Data Format:
long & Real
]
S. No.
Address
Measured parameter
words
Multiplication Factor
(if data type is long)
1
30001
Frequency
2
0.01
2
30003
1_2. PF
2
0.001
3
30005
Reserved
-
-
4
30007
3_2. PF
2
0.001
5
30009
A. PF
2
0.001
6
30011
Vrms 1*2
2
0. 1
7
30013
Vrms 3*1
2
0. 1