levels.This level allows user to select input type and some other parameters as shown
below.
LEV EL 2: Fu nctiona l Parameters Conf ig uration Part -1
Parameter
(PV d isp la y)
Setting name a nd
descr iption
(SV d isp la y)
Def ault
va lue
Sho ws on ly
if
Symbol
Name
PWD
(Pwd)
Password
0 to 9999(Password
Protection for Level-2)
-
LOCK-2 set on
in Level-3
inP
.t
(inP.t)
PV Input Type (E, J,
K, T etc.)
Follow Table-6.1
K-TC
A
.CJC
(A.CJC)
Auto Cold junction
Compensation
Yes
/
n o
1:(YES)
0: (no)
YES
Input sensor is
T/c. type
F
.CJC
(F.CJC)
Fix cold junction
Compensation
0 to 60.0 Degree
0.0
Input sensor is
T/c. type
Pv
.Hi
(Pv.Hi)
Process value range
high setting
(span > zero)
Range of the
sensor(Table 6.1) /
-1999 to 9999
(for linear input types)
1370
Pv
.Lo
(Pv.Lo)
Process value range
lower setting
-200
In
.hi
(IN.HI)
Input value range
higher setting
Input hig h va lu e (For
Lin ear t ype o nly)
0
Input is linear
type
In
.lo
(IN.LO)
Input value range
lower setting
Input lo w va lu e (For
Lin ear t ype o nly)
0
Input is linear
type
Dp
(dP)
Decimal Point
Setting
0 to 3
0
Input is linear
type
ot
(Ot)
Output Type
onof
/
P
/
nonE
0:(
onof
)
– on-off
1:(
P
)
– Proportional
Control
2:(
nonE
)
– None
0(On-off)
Pb
(Pb)
Proportional Band
0.1 to 999.9
50.0
Contro l t yp e
is P
Ct
(Ct)
Cycle Time
1 to 250 seconds
10
Control type is
P
mr
(MR)
Manual Reset
-50 to 50 %
0%
Control type is
P
HY
(HY)
hysteresis (For
On/Off control)
1 to 250
2
Control type is
on/off
PV
.SC
.
(PV.SC.)
Process value
scale
Down
/
UP
0:(down)
1:(up)
down
o
.dir
(o.dir)
Output (Cool / Heat)
Direction (Dir / Rev)
Dir
/
rev
1:(dir)
0:(rev)
Rev