27 | 50
Installation Manual LOGS50 EN_MI_090221
1.4 LOGS50 MODEL WITH INTEGRATED PRESSURE SENSOR
The commercial reference for this model is LOGS50DP83.
Model which belongs to the LOGS50 family that incorporates a built-in sensor
wired to the logger's analog input 3 (AI-3 = pressure sensor).
Sensor availability with several pressure ranges and units of measurement (Bar,
PSI…).
The process thread is 1\4 “BSP or GAS male.
System suitable for quick-coupling hose connection and for reduction fittings.
The pressure sensor used for this application by default works on 0-10 V mode
so the analog input utilized must be also 0-10 V.
The picture below shows a pressure sensor directly connected to the port and a
second option where the pressure sensor is threaded to LOGSCDP1 cable.
The terminals for this analog AI-2 (SENSOR) input - to where the pressure
sensor is connected- are directly soldered in two specific pins belonging to CDI;
connector which does not present outer accessibility for any other sensor
external connection by the user.
The analog input AI-3 for this model does not have any output pin for its exterior
physical wiring so therefore it will not be utilizable.
The general-purpose analog inputs available for this model are analog input AI-
0 and AI-1 accessible through connector DI1-AI1.