4.11 Gas Setup and Adjustment
For the Step by step process to measure
CO2
values on the Mascot ST, please refer to
Step 19 thru Step 24 in Section 4.13 of this
Installation Manual.
Offset Fire
Adjustment
Screw
Adjust ONLY when in
MIN Fire and when
using a combustion
analyzer.
See Section 4.12 for
step by step details.
Inlet Gas
pressure port
Table 10.
CO2 Values
Table 12.
Manifold Pressures
WARNING
Installer is required to verify combustion settings as part of
the installation process. CO should not exceed 300 ppm.
Standard Factory Setting is for MIN Fire. 9.0% CO
2
@ 0 - 2,000 ft altitude (Natural Gas).
4.10 Gas Supply Pressure
Refer to the illustration. Check the gas inlet pressure
measurement from inlet gas pressure port.(Loosen the
port bolts before you check the gas inlet pressure.)
1. The appliance and its individual shutoff valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 psi (3.5 kPa).
2. The appliance must be isolated from the gas supply
piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 psi (3.5 kPa).
Natural Gas
LP Gas
Maximum
Pressure
10.5˝
WC
Maximum
Pressure
13.0˝
WC
Minimum
Pressure
3.5˝
WC
Minimum
Pressure
8.0˝
WC
Table 11.
Min and Max Inlet Gas Line Pressures
Customer Service and Product Support:
800.900.9276 • Fax 800.559.1583
Headquarters:
20
Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1503 Document 4286
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
•
Fax 905.366.0130
www.Laars.com
Document 4286
M
ascot ST Gas Conversion Kit
pg 4 of 4
Table C
Table D
Figure E (Conversion label)
25.
Once the CO2 and manifold pressure
measurements for both MIN and MAX Fire are
correct (for your altitude) turn OFF the Control
Display
and set DIP switches 6 and 7 to the
OFF position for Nominal Fire (normal operation).
Turn the Control Display
back on when done.
26.
Write in the correct Conversion Date and the
Technicians Name to the included gas conversion
sticker. See Figure E. Then apply that sticker
adjacent to the rating plate.
27.
Put the water heater cover back on and assemble/
tighten the 4 screws that hold the cover in place.
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
WARNING
Always make sure that the Control Display is turned
OFF
before changing any DIP switch. Then turn Control
Display back ON to continue with CO2
measurements.
High Altitude
Setting level
‘LP’
CO2
Values
‘NG’
CO2
Values
MSTWW199
2" or 3" VENT
2" or 3" VENT
0~2,000 ft
10.7
MAX
10
9.7
MIN
8.5
2,000~5,000 ft
10.2
MAX
9.1
10.3
MIN
9.7
5,000~8,000 ft
10.3
MAX
9.1
10.4
MIN
9.8
8,000~10,000 ft
10.5
MAX
9
10.6
MIN
9.8
AVERTISSEMENT
Ce conversion doit être installé par un organisme de
service conformément aux instructions du fabricant
et tous les codes et les exigences de l’autorité
compétente. Si les informations contenues dans ces
instructions n’est pas suivi à la lettre, un incendie,
une explosion ou de la production de monoxyde
de carbone mais résultat causant des dommages
matériels, des blessures ou des pertes de vie. Le
service est responsable pour la bonne et complète
l’installation de ce kit. L’installation n’est pas correcte
et complète jusqu’à ce que le fonctionnement de
l’appareil converti est vérifi ée comme
spécifi é dans
le manuel d’instruction fourni avec le
kit.
Manifold pressure
‘NG’ type combustibility
‘LP’ type combustibility
MSTWW199
MAX FIRE
-0.11” to -0.17” WC
-0.07” to -0.11” WC
MIN FIRE
-0.10” to -0.16” WC
-0.06” to -0.10” WC
H2373700-
Customer Service and Product Support:
800.900.9276 • Fax 800.559.1583
Headquarters:
20
Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1503 Document 4286
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
•
Fax 905.366.0130
www.Laars.com
Document 4286
M
ascot ST Gas Conversion Kit
pg 4 of 4
Table C
Table D
Figure E (Conversion label)
25.
Once the CO2 and manifold pressure
measurements for both MIN and MAX Fire are
correct (for your altitude) turn OFF the Control
Display
and set DIP switches 6 and 7 to the
OFF position for Nominal Fire (normal operation).
Turn the Control Display
back on when done.
26.
Write in the correct Conversion Date and the
Technicians Name to the included gas conversion
sticker. See Figure E. Then apply that sticker
adjacent to the rating plate.
27.
Put the water heater cover back on and assemble/
tighten the 4 screws that hold the cover in place.
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
WARNING
Always make sure that the Control Display is turned
OFF
before changing any DIP switch. Then turn Control
Display back ON to continue with CO2
measurements.
High Altitude
Setting level
‘LP’
CO2
Values
‘NG’
CO2
Values
MSTWW199
2" or 3" VENT
2" or 3" VENT
0~2,000 ft
10.7
MAX
10
9.7
MIN
8.5
2,000~5,000 ft
10.2
MAX
9.1
10.3
MIN
9.7
5,000~8,000 ft
10.3
MAX
9.1
10.4
MIN
9.8
8,000~10,000 ft
10.5
MAX
9
10.6
MIN
9.8
AVERTISSEMENT
Ce conversion doit être installé par un organisme de
service conformément aux instructions du fabricant
et tous les codes et les exigences de l’autorité
compétente. Si les informations contenues dans ces
instructions n’est pas suivi à la lettre, un incendie,
une explosion ou de la production de monoxyde
de carbone mais résultat causant des dommages
matériels, des blessures ou des pertes de vie. Le
service est responsable pour la bonne et complète
l’installation de ce kit. L’installation n’est pas correcte
et complète jusqu’à ce que le fonctionnement de
l’appareil converti est vérifi ée comme
spécifi é dans
le manuel d’instruction fourni avec le
kit.
Manifold pressure
‘NG’ type combustibility
‘LP’ type combustibility
MSTWW199
MAX FIRE
-0.11” to -0.17” WC
-0.07” to -0.11” WC
MIN FIRE
-0.10” to -0.16” WC
-0.06” to -0.10” WC
H2373700-
Summary of Contents for MSTWW
Page 38: ...LAARS Heating Systems Page 36 4 19 Wiring Diagram Figure 3 Wiring Diagram...
Page 39: ...Mascot ST Tankless Water Heater Page 37 4 20 Ladder Diagram Figure 4 Ladder Diagram...
Page 63: ...Mascot ST Tankless Water Heater Page 61 Cover Assembly...
Page 66: ...LAARS Heating Systems Page 64 Notes...
Page 67: ...Mascot ST Tankless Water Heater Page 65 Notes...