Page 6
Commander UCP 5000 / 5100 Series
3 Operation
Power
Au
x 1
Control
Lamp
Test
PDU Outlet Power
Control
Breaker
On
Off
EPO Reset
Audio
On
Off
HOURS
QUARTZ
1/10
PRESS
RESET
Commander
Enable
Disable
Return
Enable
Return
Outlet Control Bus
J1
J2
J4
J5
J3
Remote EPO Input
Outlet Control Bus
Au
x 2
1
2
3
13
4
6
7
8
9
10
11
12 15 14
5
3.1 Startup
When power is applied to the UCP (and assuming the
Control Breaker
is engaged), the
Control Power
lamp will be lit
indicating the system is powered. This indicator also functions as a lamp and audible alarm test button. Pressing
Control
Power
will momentarily illuminate all indicators, and trigger the audible alarm.
All normally closed (N.C.) -001 models power up in the EPO mode — as though the EPO button had
been pressed. The
EPO Reset
button must be pressed before beginning normal operation.
3.2 Control Modes and Connector Pins
The system has three modes or states of control named On, Off, and EPO. These modes change the state of the Outlet
Control Bus pins at the rear of the unit—which are then interpreted by the remote EPO controller in a Marway PDU (or
other equipment with compatible signals).
The following table summarizes the pin connections during the operating modes.
UCP State
–000 Normally Open
–001 Normally Closed
J1 & J2
J3 & J4
J1 & J2
J3 & J4
Startup
no connections
no connections
no connections
1
no connections
PDU Power On
Enable–Return
Enable–Return
Enable–Return
Disable–Return
Enable–Return
PDU Power Off
no connections
no connections
Disable–Return
no connections
EPO active
Disable–Return
no connections
no connections
no connections
1 — For N.C. models, no connection on all pins is an EPO state. EPO Reset must be pressed at each new startup.
A –000 normally open (NO) UCP should be paired with PDUs equipped with a NO EPO controller.
A –001 normally closed (NC) UCP should be paired with PDUs equipped with a NC EPO controller.