background image

6

GPac Users Information 7/07-2

The GPac air conditioner with gas heat is equipped with an automatic spark ignition system. There is no pilot. 

In case of a safety shutdown on units with electronic temperature control, shut main disconnect 

OFF

 and then 

back 

ON

 to reset ignition control. On units with an electro-mechanical thermostat, move the thermostat switch 

to 

OFF

 and return the thermostat switch to 

HEAT

. On initial start-up of the unit in the heating mode, a burn-off 

of excess paint and oils remaining from the manufacturing process may cause some smoking and smell for 5-10 

minutes. 

Cooling Cycle

1.  Set the fan switch to "Auto" and the system switch to "Off".
2.  Move the cooling temperature on the wall thermostat to a point 

higher

 than the room temperature.  Move 

the heating temperature to a temperature that is 

lower

 than the room temperature.

3.  Set the thermostats system switch to "Cool" or "Auto" position.  Nothing should operate at this time.
4.  Set the time delay in the control box to three minutes.  Note that time delay is an option on some GPac 

units and may not be on your air conditioner.

5.  Remove the cover plate from the thermostat.  Slowly lower the thermostat cooling temperature.  Once the 

indoor fan turns on, allow approximately three minutes for the compressor and outdoor fan to start.

For units equipped with the low ambient control, note that the outdoor fan may not come on immediately, because 

it is cycled by refrigerant pressures.  Some units have a time delay module which prevents the compressor from 

restarting immediately after interruption of power.  See 

Cooling Mode

 section of the Installation Instructions for 

details on the operation of the low ambient control and the time delay.

Heating Cycle

1.  Turn off electrical power to the unit. 
2.  Set thermostat to its lowest setting.
3.  Remove heat section access panel. 
4.  Turn knob on the gas control valve to ON. Do not force. Never light the burner with a match or torch.

Figure 2. Gas Control Valve

5.  Replace heat section access panel.
6.  Turn on electrical power to the unit.
7.  Set room thermostat to desired temperature. 
8.  On a call for heating, the air switch closes, initiating a 30 second pre-purge.
9.  At end of pre-purge period, the Spark and Gas valve is energized for up to a 5 second ignition trial. Gas 

valve will open.

10. Burners ignite and carryover.

ON SWITCH

Summary of Contents for AVG24

Page 1: ...on in these instructions are not followed exactly a fire carbon monoxide poisoning or explosion may result causing property damage personal injury or loss of life Read all instructions carefully prior...

Page 2: ...installation r glage alt ration intervention ou entretien peut causer d g ts mat riels et dommages corporels ou m me mort Installation et interventions doivent tre effectu es par un installateur ou un...

Page 3: ...s le voyez sur l unit GPac et dans les manuels d instructions soyez conscient du risque de blessure personnelle Assimilez la signification des mots de mise en garde DANGER AVERTISSEMENT et ATTENTION I...

Page 4: ...ut off the gas valve to the unit before shutting off the electrical supply 7 Become familiar with all controls and shut off valves Make sure you know how to shut off gas and electrical power to the un...

Page 5: ...n appearance The flame should be in the middle of the heat exchanger tubes Check to see that all the burners are lit and that the flame does not impinge on the sides of the heat exchanger Observe the...

Page 6: ...not be on your air conditioner 5 Remove the cover plate from the thermostat Slowly lower the thermostat cooling temperature Once the indoor fan turns on allow approximately three minutes for the comp...

Page 7: ...will remain energized but the gas valve will not be energized until the cause of the false flame is removed 3 If the air pressure switch is closed when the inducer is energized or does not close after...

Page 8: ...it should be maintained as follows Air Filter Replace the air filter whenever it is visibly dirty Note Filters must be U L C approved or equivalent for use in Canada Indoor Coil If the coil becomes cl...

Page 9: ...eason to ensure proper burner operation Light the burners and allow the unit to operate for a few minutes to establish normal burning conditions Look at the flames on the burners They should be predom...

Page 10: ...sisted The installation of the furnace vent must be in accordance with the National Fuel Gas Code NFGC ANSI Z223 1 2000 NFPA54 2002 and or Section 7 andAppendix C of the CSAB149 1 00 National Standard...

Page 11: ...70080 Low Pressure Control 35 Open 60 Close 70050 70050 70050 Filter 2 Thick 81257 2 81257 2 81257 2 18 x 24 18 x 24 18 x 24 Motor Economizer EPA 40101 40101 40101 Enthalpy Control H205A EC 70230 702...

Page 12: ...ontrol High 67 500 Btu Hr n a n a n a Limit Control High 90 000 Btu Hr n a n a n a Limit Control High 75 000 Btu Hr 70372 Limit Control High 100 000 Btu Hr 70372 Limit Control High 125 000 Btu Hr 7037...

Page 13: ...uct may ship the allegedly defective or malfunctioning product or part to Marvair at such owner s expense and Marvair will diagnose the defect and if the defect is covered under this warranty Marvair...

Reviews: