background image

5

GPac Users Information 7/07-2

c.  The supply air and return air duct connections to verify that they are physically sound, are sealed to the 

furnace casing. (See 

Porting and Ductwork

 section of the Installation Instructions.)

d.  To make certain that there are no signs of deterioration of the unit and that the unit is physically sound 

without cracks, gaps or sagging.  

e.  The condensate line to make sure that condensate can flow free from the unit and the line is not 

obstructed.

f.  The air filters to make certain that they are not dirty. Clean and/or replace as required. The fiberglass 

disposable type should be REPLACED before they become clogged. Dirty filters are can severely 

restrict air flow and are a common cause of complaints of inadequate heating and cooling.

  Filters are located behind the front panel. To change the filter, remove the front panel and slide the 

filters out. Replacement filters should be ONLY of the type and size as the original Marvair supplied 

filters.  

g.  To verify that the burner flame is in good adjustment. 
  Allow the unit to operate for a few minutes to establish normal burning conditions. Look at the flames 

on the burners. They should be predominately blue in color and robust in appearance. The flame 

should be in the middle of the heat exchanger tubes. Check to see that all the burners are lit and that 

the flame does not impinge on the sides of the heat exchanger.  Observe the flame. There should be 

little or no change to in the shape or size of the flame. Changes in the shape and size of the flame may 

indicate a leak in the heat exchanger. See figure 1.

  Distorted flame or yellow tips of the natural gas flame or long yellow tips on LP gas flames may be 

caused by one or more of the following:

  1.  lint or dirt inside the burner or burner ports,
  2.  lint or dirt at the air inlet between the burner and the manifold pipe, or
  3.  an obstruction over the burner plate.

If any of these are visible, turn the unit off and use a vacuum or a soft brush to clean the affected areas.

It is recommended that the unit be inspected by a qualified service technician to thoroughly check and inspect 

the unit prior to each heating season. 

Figure 1. Burner Flame

Start-up

Before lighting the unit, smell around the unit for gas. Be sure to smell next to the floor because LP gas is heavier 

than air and will settle on the floor.

The gas valve on your unit is equipped with an ON/OFF knob. Use only your hand to turn the knob  Never use 

tools. If the knob will not push in or turn by hand, do not try to repair it. Call a qualified service technician. Force 

or attempted repair may result in a fire or explosion.

Summary of Contents for AVG24

Page 1: ...on in these instructions are not followed exactly a fire carbon monoxide poisoning or explosion may result causing property damage personal injury or loss of life Read all instructions carefully prior...

Page 2: ...installation r glage alt ration intervention ou entretien peut causer d g ts mat riels et dommages corporels ou m me mort Installation et interventions doivent tre effectu es par un installateur ou un...

Page 3: ...s le voyez sur l unit GPac et dans les manuels d instructions soyez conscient du risque de blessure personnelle Assimilez la signification des mots de mise en garde DANGER AVERTISSEMENT et ATTENTION I...

Page 4: ...ut off the gas valve to the unit before shutting off the electrical supply 7 Become familiar with all controls and shut off valves Make sure you know how to shut off gas and electrical power to the un...

Page 5: ...n appearance The flame should be in the middle of the heat exchanger tubes Check to see that all the burners are lit and that the flame does not impinge on the sides of the heat exchanger Observe the...

Page 6: ...not be on your air conditioner 5 Remove the cover plate from the thermostat Slowly lower the thermostat cooling temperature Once the indoor fan turns on allow approximately three minutes for the comp...

Page 7: ...will remain energized but the gas valve will not be energized until the cause of the false flame is removed 3 If the air pressure switch is closed when the inducer is energized or does not close after...

Page 8: ...it should be maintained as follows Air Filter Replace the air filter whenever it is visibly dirty Note Filters must be U L C approved or equivalent for use in Canada Indoor Coil If the coil becomes cl...

Page 9: ...eason to ensure proper burner operation Light the burners and allow the unit to operate for a few minutes to establish normal burning conditions Look at the flames on the burners They should be predom...

Page 10: ...sisted The installation of the furnace vent must be in accordance with the National Fuel Gas Code NFGC ANSI Z223 1 2000 NFPA54 2002 and or Section 7 andAppendix C of the CSAB149 1 00 National Standard...

Page 11: ...70080 Low Pressure Control 35 Open 60 Close 70050 70050 70050 Filter 2 Thick 81257 2 81257 2 81257 2 18 x 24 18 x 24 18 x 24 Motor Economizer EPA 40101 40101 40101 Enthalpy Control H205A EC 70230 702...

Page 12: ...ontrol High 67 500 Btu Hr n a n a n a Limit Control High 90 000 Btu Hr n a n a n a Limit Control High 75 000 Btu Hr 70372 Limit Control High 100 000 Btu Hr 70372 Limit Control High 125 000 Btu Hr 7037...

Page 13: ...uct may ship the allegedly defective or malfunctioning product or part to Marvair at such owner s expense and Marvair will diagnose the defect and if the defect is covered under this warranty Marvair...

Reviews: