Exterior Wash

TM

 200 Series User Manual 

15 

Control data link 

 

Warning! Make sure that data connections are totally protected from water, or 
moisture may be drawn up the inside of the cable by the vacuum created by normal 
heating and cooling. 

Connecting the data link 

The fixture has a 1.8 m (5.9 ft.) shielded cable with 2 pairs of wire for data connection. The pair of wires 
marked with a short length of red insulation is for data input. The other pair, marked with a short length of 
black insulation, is the output to the next device in the daisy chain.  

 

DMX cable details 

 

Data cabling may be connected directly in weatherproof junction boxes or fitted with weatherproof XLR 
connectors. Protect connectors in a weatherproof housing if they are not totally weatherproof.  

Connect the cable as shown in the table below. Do not connect the shield conductor to ground (earth) or 
allow it to come into contact with a connector shell, as this may cause interference. 

 

Wires 

Input pair (red tube) 

Output pair (black tube) 

Shield 

Color 

white 

green 

white 

brown 

black 

Signal 

DMX in + 

DMX in - 

DMX out + 

DMX out - 

common 

Male XLR pin 

pin 3 

pin 2 

pin 1 

Female XLR pin 

pin 3 

pin 2 

pin 1 

Data connections 

 

The following considerations must be taken into account when laying out the data network: 

 

512 DMX channels are available in a single DMX universe. If the total combined channel requirements of 
all connected fixtures exceeds 512, one or more additional DMX universes will be required. 

 

One may reliably connect up to 32 fixtures in a single daisy chain.  

 

Use RS-485 data cable designed for exterior use. RS-485 cable has low capacitance and a characteristic 
impedance of 85 to 150 Ohms. It is electrically shielded and has at least 1 twisted pair of conductors. The 
minimum recommended wire size is 0.25 mm2 (24 AWG) for runs up to 200 meters (1000 ft.) and 0.32 
mm2 (22 AWG) for runs up 500 meters (1640 ft).  

 

Branches may be added to the link using an opto-isolated splitter. To preserve RDM functionality, use an 
RDM compatible amplifier-splitter such as the Martin 

5.5 Splitter™. Each branch may itself connect up to 

32 fixtures.  

 

An RDM amplifier may also be used to extend a network beyond 500 meters (1640 ft.) or to connect up to 
32 additional fixtures to the daisy chain.  

 

The data link and each connected branch must be terminated at the end by placing a 120 ohm resistor 
(available from Martin, P/N 04150308) across the data output hot (+) and data output cold (-) conductors of 
the last fixture on the chain.  

 

Long parallel runs of AC power and control data cables may cause interference on the data link and must 
be avoided. Even if not required by law, use separate conduits for power and data cables. 

 

The combined data input/output cable does not support the second DMX data pair. Do not place devices 
that use the second DMX data pair (connected to XLR pins 4 & 5) on the same daisy chain as Exterior 
Wash

  fixtures. 

Summary of Contents for ExteriorWash 200 Series

Page 1: ......

Page 2: ...t loss consequential or economic loss or any other loss occasioned by the use of inability to use or reliance on the information contained in this manual Martin Harman and all other trademarks in this...

Page 3: ...Connecting to power 13 Control data link 15 Connecting the data link 15 Setup 16 Accessing and navigating the control menus 16 DMX settings 16 Programming a standalone show 17 Manual mode 17 Display s...

Page 4: ......

Page 5: ...the safety precautions below are not followed Install operate and service Martin products only as directed in their user manuals or you may create a safety hazard or cause damage that is not covered b...

Page 6: ...the fixture Do not illuminate surfaces within 20 cm 8 in of the fixture Do not attempt to bypass thermostatic switches or fuses Do not modify the fixture in any way not described in this manual or in...

Page 7: ...on responses blink reflex and reaction to skin discomfort can protect them At distances greater than 2 2 m 7 3 ft potential eye and skin injury hazards from the light output are normally prevented by...

Page 8: ...attachment such as a safety cable inserted through the secondary attachment point that will hold the fixture if a primary attachment fails The secondary attachment must be approved by an official bod...

Page 9: ...access They are prepared for hard wiring with 1 8 m 5 9 ft cables for power and data connection Fixture overview Number Description 1 Front ring with recessed channel for optional diffuser lenses 2 Ti...

Page 10: ...ning All fasteners used to mount Exterior Wash 200 Series fixtures must be corrosion resistant and strong enough to mount the fixture safely A washer must be installed directly under the head of each...

Page 11: ...e fixture can become hot Wear heat resistant gloves if you adjust the aim of the fixture when it is or has recently been powered on Tilt adjustment can be carried out with the fixture powered on as fo...

Page 12: ...nt ring 4 Press the diffuser lens gasket firmly into the recess in the front ring 5 Either place a trim ring over the diffuser and fasten with provided hardware or install a snoot as described below A...

Page 13: ...0 Hz Do not connect to power at any other voltage or frequency You can connect the Exterior Wash 200 Series to a single phase live neutral ground earth or to one phase of a grounded earthed three phas...

Page 14: ...grounding type earthed plug with integral cable grip that is rated minimum 277 V 6 A Follow the plug manufacturer s instructions and connect the wires in the power cable as shown in this table Live or...

Page 15: ...ombined channel requirements of all connected fixtures exceeds 512 one or more additional DMX universes will be required One may reliably connect up to 32 fixtures in a single daisy chain Use RS 485 d...

Page 16: ...r Exterior Wash 210 channel mode from the control panel 1 Press and hold the MENU button to access the control menu If prompted for a password press the arrow buttons to scroll to the 3 digit password...

Page 17: ...press MENU again to return to the PROGRAM SHOW menu 4 To modify scene transitions select FADE TIME and press ENTER Press UP or DOWN to select a fade time from 0 to 120 seconds Press ENTER 5 To modify...

Page 18: ...red by the product warranty To operate fixtures in master slave mode the fixtures must be connected as described under Control data link on page 15 The master fixture must be programmed to run a stand...

Page 19: ...X signal or if the DMX signal is suddenly lost Note that for stand alone and master slave operation DMX STATE must be set to SHOW MODE SHOW MODE Fixture executes programmed scenes HOLD LAST LOOK Fixtu...

Page 20: ...YES and press ENTER to confirm or MENU to escape Setup via RDM The Exterior Wash 200 Series is compatible with RDM Remote Device Management Using an RDM compliant DMX controller you can communicate w...

Page 21: ...ce schedule Do not use products that contain solvents abrasives or caustic agents for cleaning as they can cause surface damage to the fixture The aluminum housing and front glass can be cleaned with...

Page 22: ...intensity on channel 1 Channel Value Function 1 0 255 Dimmer 0 100 2 0 255 Red 0 100 3 0 255 Green 0 100 4 0 255 Blue 0 100 5 0 255 White 0 100 Exterior Wash 220 The DMX protocol provides individual 0...

Page 23: ...ayed Manual Mode 200 210 Red 0 255 Manually adjust output Green 0 255 Blue 0 255 White 0 255 Manual Mode 220 Warm White 0 255 Manually adjust output Cold White 0 255 Display Setting Display Inverse No...

Page 24: ...fig contd DMX State Show Mode Behavior when no DMX control signal present Hold Last Look Black Out Display Lock No Yes Password protect control menu Lock Password 0 999 123 Set user password Factory R...

Page 25: ...nk defective Check number of DMX channels required by each fixture and check DMX addresses on fixtures and DMX controller Verify CHANNEL MODE setting Inspect connections and cables Correct poor connec...

Page 26: ...DM compliance ANSI ESTA E1 20 Exterior Wash 200 and 210 DMX channels 4 or 5 Exterior Wash 220 DMX channels 3 Optics All models Minimum LED lifetime 50 000 hours to 70 luminous output Figure obtained u...

Page 27: ...200 100 V 60 Hz 1 6 A 160 W PF 0 99 120 V 60 Hz 1 4 A 160 W PF 0 99 230 V 50 Hz 0 8 A 160 W PF 0 94 277 V 60 Hz 0 7 A 160 W PF 0 89 Exterior Wash 210 100 V 60 Hz 1 5 A 148 W PF 0 99 120 V 60 Hz 1 3 A...

Page 28: ...Exterior Wash 200 7 EU aluminum P N 90509087 Exterior Wash 200 7 US aluminum P N 90509090 Exterior Wash 210 10 EU aluminum P N 90509088 Exterior Wash 210 10 US aluminum P N 90509095 Exterior Wash 220...

Page 29: ...his product If it becomes difficult or impossible to read it must be replaced using the illustration below to reproduce a new label sized 58 x 16 mm in black with a yellow border RISK GROUP 3 WARNING...

Page 30: ...30 Exterior WashTM 200 Series User Manual...

Page 31: ......

Page 32: ...www martin com Olof Palmes All 18 8200 Aarhus N Denmark Tel 45 8740 0000 Fax 45 8740 0010...

Reviews: