background image

Page 1 from 4

922044006_09_024

 SLD-34/SP

SLD-44/SP

 SLD-28/SP

220-240V AC/50-60Hz

3h

24h

Overcharging and deep discharging protection

Charge LED, Lamp LED, Fault LED, Test Button

IP30

3.6V/1.5Ah

100lm /100lm 

125lm /125lm 

9.5 VA

9 VA

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838

5 to 40  C

o

up to 95% 

Bayblend FR3010, aluminum, plexiglas

280x120x15mm

3 years (1 year for the battery)

790gr.

1110gr.

1580gr.

340x190x15mm

440x240x15mm

289x65x34mm

TECHNICAL CHARACTERISTICS 

(for LED MODULE specifications see page 4)

SELF TESTING MAINTAINED EMERGENCY ILLUMINATION SIGNS WITH WHITE LEDs

 GENERAL

The  luminaire  consists  mainly  from  two 

Battery Cut-off

parts,  the  body,  where  all  the  electronics 

The luminaire enters in this operation when 

are  located  and  the  lamp-head  where  the 

the  mains  power  supply  fails  and  battery 

indication  sign  and  the  high  efficiency 

has  lost  its  energy.  During  this  operation 

LEDs are located.

the  luminaire  enters  the  idle  state  and 
battery  consumption  is  negligible,  in  order 

Maintained to non-maintained selection 

to be protected from deep discharge.

capability

Power 

on 

the 

device 

and 

press 

  Manual Test

continuously  the  TEST  button  for  10 

The manual test can be conducted only if 

seconds,  until  the  led  strip  turns  off. 

the mains power supply and the battery is 

Release  the  button  and  after  a  short 

connected. By pressing the test button 

emergency  test,  the  device  operates  as 

briefly an operation test is initiated. During 

non  maintained.  If  you  want  to  restore  the 

this test period all indication LEDs are 

previous  condition  (maintained  operation), 

OFF.

press continuously the TEST button for 10 
seconds,  until  the  led  strip  lights.  Release 

Automatic Operatioanal Test

the  button  and  after  a  short  emergency 

This  test  includes  all  the  operations  that 

test,  the  device  operates  as  maintained 

provide  the  manual  test  and  is  conducted 

illumination sign.

automatically every 15 days. In order to be 
performed,  the  mains  power  supply  and 

Battery Charging

the battery should be connected.

The 

battery 

charging 

is 

completely 

 

controled.  In  this  case,  is  achieved  the 

Automatic Autonomous Test

perfect battery maintenance , as well as the 

The Automatic Autonomous Test is 

elongation  of  its  duration.  When  the  battery 

conducted and measures the luminaire`s 

has  completely  charged,  it  charges  with  a 

back up operation. This test is conducted 

maintenance current.

automatically every six months. In order to 

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

Operation  temperature range

Relative humidity
Construction materials
External panel's dimensions
External unit’s dimensions
Typical weight
Guarantee

Mains voltage

Maximum power consumption
Battery (Ni-MH)

Recharging  time

Battery protection
Indications

Minimum emergency duration

Degrees of cover protection
Produced in accordance with 

Light source intensity (230V) / (emerg.)