55908059-01
35
47.
Have the charging hoses been removed safely
and with minimum loss of refrigerant?
If yes go to question 48
If no rectify and reassess
48.
Is the service valve leak free and cap replaced?
If yes go to question 49
If no go to question 50
REFRIGERANT RECOVERY
49.
Have all of the tools, refrigerant and equipment
been removed from site?
If yes end assessment
If no rectify and reassess
50.
Is the area adequately ventilated?
If yes go to question 51
If no rectify and reassess
51.
Has a suitable flammable gas leak detector been
energised and placed at a low level?
If yes go to question 52
If no rectify and reassess
52.
Has a suitable recovery unit been fitted?
If yes go to question 53
If no rectify and reassess
53.
Do you have a suitable recovery cylinder with
adequate capacity?
If yes go to question 54
If no rectify and reassess
54.
Have you placed it on to a suitable calibrated
weighing platform?
If yes go to question 55
If no rectify and reassess
55.
Calibration certificate number
56.
Have you documented the amount of refrigerant
recovered and filled out the appropriate
paperwork?
If yes go to question 57
If no rectify and reassess
57.
Identify source of leakage and recommence
assessment procedure.
This information is to be given to the end user along with any other risks identified.
Summary of Contents for A2LCELLARMATCH
Page 1: ...55908059 01 A2LCELLARMATCH TECHNICAL MANUAL ...
Page 12: ...55908059 01 12 2G CONDENSING UNIT WIRING DIAGRAMS ...
Page 14: ...55908059 01 14 ...
Page 22: ...55908059 01 22 2K COMPONENT IDENTIFICATION SMC ...
Page 31: ...55908059 01 31 3H EVAPORATOR WIRING DIAGRAM 3I REFRIGERANT SYSTEM SCHEMATIC DIAGRAM ...