55908059-01
18
C
Valve position in stand-by
0 = 25%
1…100% = % opening
50%
0
100
%
I
91
218
C
start-up delay after defrost
10
0
60
min
I
40
167
A
Pre-position time
6
0
18000
s
I
90
217
A
Hot gas bypass temperature set point
10
-85(-121)
200 (392)
°C (°F)
A
28
27
A
Hot gas bypass pressure set point
3
-20 (-290)
200 (2900)
barg (psig)
A
62
61
A
EPR pressure set point
3.5
-20 (-290)
200 (2900)
barg (psig)
A
29
28
C
PID proportional gain
15
0
800
-
A
48
47
C
PID integral time
150
0
1000
s
I
38
165
C
PID derivative time
5
0
800
s
A
49
48
A
LowSH protection threshold
5
-40 (-72)
superheat set
point
K(°F)
A
56
55
C
LowSH protection integral time
15
0
800
s
A
55
54
A
LOP protection threshold
-50
-85(-121)
MOP protec-
tion threshold
°C (°F)
A
52
51
C
LOP protection integral time
0
0
800
s
A
51
50
A
MOP protection threshold
50
LOP protection
threshold
200 (392)
°C (°F)
A
54
53
C
MOP protection integral time
20
0
800
s
A
53
52
A
Enable manual valve position
0
0
1
-
D
24
23
A
Manual valve position
0
0
9999
step
I
39
166
C
Discharge superheat setpoint
35
-40(-72)
180 (324)
K (F°)
A
100
99
C
Discharge temperature setpoint
105
-85(-121)
200 (392)
°C (°F)
A
101
100
C
Liquid level perc. set point
50
0
100
%
A
118
117
ADVANCED
A
High Tcond threshold
80
-85(-121)
200 (392)
°C (°F)
A
58
57
C
High Tcond integral time
20
0
800
s
A
57
56
A
Modul thermost setpoint
0
-85(-121)
200 (392)
°C (°F)
A
61
60
A
Modul thermost di
ff
erential
0, 1
0.1 (0.2)
100 (180)
°C (°F)
A
60
59
C
Modul thermost SHset o
ff
set
0
0 (0)
100 (180)
K (°F)
A
59
58
C
CO
2
regul. 'A' coe
ffi
cient
3.3
-100
800
-
A
63
62
C
CO
2
regul. 'B' coe
ffi
cient
-22.7
-100
800
-
A
64
63
C
Start manual tuning 0 = no; 1= yes
0
0
1
-
D
39
38
-
C
Tuning method
0…100= automatic selection
101…141= manual selection
142…254=not accepted
255= PID parameters identified model
50
0
255
-
I
79
206
-
C
Network settings
0= 4800; 1= 9600; 2= 19200; 4 = 4800 bps; 5= 9600 bps;
6= 19200 bps; 16= 4800 bps; 17= 9600 bps; 18= 19200 bps;
20= 4800 bps; 21= 9600 bps; 22= 19200 bps; 24= 4800 bps;
25= 9600 bps; 26= 19200 bps; 28= 4800 bps; 29= 9600 bps;
30= 19200 bps.
2
0
30
bit/s
I
74
201
CO
A
Power supply mode
0= 24 Vac; 1= 24 Vdc
0
0
1
-
D
47
46
C
Enable mode single on twin (parameter disabled)
0= Twin; 1= Single
0
0
1
-
D
58
57
C
Stop manual positioning if net error
0 = Normal operation; 1 = Stop
0
0
1
-
D
59
58
C
Programmable regulation configuration
0
0
32767
-
I
101
228
C
Programmable regulation input
0
0
32767
-
I
102
229
C
Programmable SH regulation options
0
0
32767
-
I
103
230
C
Programmable regulation set point
0
-800(-11603)
800(11603)
-
A
112
111
C
Faulty closure alarm status
0/1=no/yes
0
0
1
-
D
49
48
Summary of Contents for A2LCELLARMATCH
Page 1: ...55908059 01 A2LCELLARMATCH TECHNICAL MANUAL ...
Page 12: ...55908059 01 12 2G CONDENSING UNIT WIRING DIAGRAMS ...
Page 14: ...55908059 01 14 ...
Page 22: ...55908059 01 22 2K COMPONENT IDENTIFICATION SMC ...
Page 31: ...55908059 01 31 3H EVAPORATOR WIRING DIAGRAM 3I REFRIGERANT SYSTEM SCHEMATIC DIAGRAM ...