-5-
AIRFLOWS HL/HLR UNITS
Minimum
Medium
Maximum
HL/HLR
CFM
m
3
/s
CFM
m
3
/s
CFM
m
3
/s
380
805
0.38
1000
0.47
1145
0.54
460
850
0.40
1100
0.52
1400
0.66
540
1000
0.47
1290
0.61
1650
0.78
AIRFLOWS OUTDOOR UNITS
MIN Speed
MAX Speed
Model
CFM
m
3
/s
CFM
m
3
/s
MCU(+) 90
--
1440
0.68
2420
1.14
MCU(+) 100
MHPUE 90
1440
0.68
2420
1.14
MCU(+) 130
MHPUE 100
2840
1.34
3690
1.74
MCU(+) 165
MHPUE 130
2840
1.34
3690
1.74
SOUND PRESSURE LEVELS HL/HLR UNITS
Sound Pressure Levels
MODEL
Speed
dBA
NC
380
Min
50
42
Med
53
47
Max
57
51
460
Min
47
41
Med
53
47
Max
59
53
540
Min
48
42
Med
53
48
Max
59
53
Sound Pressure Levels are dB relative to 2 x 10
-5
N/m
2
and are calculated from the results under anechoic conditions and are
quoted as an average of all points on a hemisphere of a radius of 3m away from the centre of the unit.
SOUND POWER and SOUND PRESSURE LEVELS
550/551 SERIES MCU, MCU+ and MHPUE
MAXIMUM SPEED
SOUND POWER LEVELS
SOUND PRESSURE
LEVELS
Frequency Hz
MCU(+)
MHPUE
Compressor
125
250
500
1K
2K
4K
dBA
dBA
NC
90
90
Scroll
81.8
71.8
69.2
68.6
63.1
57.4
72.8
52.3
47
100
--
Scroll
79.4
73.7
71.5
68.5
63.8
58.1
73.4
52.9
47
--
100
Scroll
79.0
69.7
68.6
65.9
61.2
55.2
71.0
50.5
44
130
130
Scroll
73.0
70.3
70.0
68.8
65.0
56.7
72.6
52.1
47
165
--
Scroll
73.1
70.3
70.1
68.9
65.5
57.5
73.1
57.2
51
MINIMUM SPEED
SOUND POWER LEVELS
SOUND PRESSURE
LEVELS
Frequency Hz
MCU(+)
MHPUE
Compressor
125
250
500
1K
2K
4K
dBA
dBA
NC
90
90
Scroll
79.0
65.4
64.9
61.5
58.5
53.7
67.6
47.1
40
100
--
Scroll
75.3
69.4
70.9
63.7
59.7
53.6
70.4
49.9
46
--
100
Scroll
67.1
67.9
65.0
61.2
56.3
51.0
66.9
46.4
40
130
130
Scroll
65.4
66.7
68.1
66.1
63.1
53.0
70.0
49.5
44
165
--
Scroll
65.5
66.9
67.3
65.1
64.2
54.0
72.6
52.6
47
Sound Power Levels were obtained in full accordance with the direct method of ISO 3741: 1988. Quantities are shown in dB with
a standard reference of 1 pW.
Sound Pressure Levels are dB relative to 2 x 10
-5
N/m
2
and are calculated from the results under free field conditions and are quoted
as an average of all points on a sphere of a radius of 3m away from the centre of the unit (in cooling mode); (add 3dBA or 3NC for
units at an intersection of a wall, add 1dBA or 1NC for high level wall mounted units).
Summary of Contents for 526 HL Series
Page 13: ... 13 ...
Page 16: ... 16 HL WIRING DIAGRAM HLR WIRING DIAGRAM ...
Page 17: ... 17 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 18: ... 18 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 19: ... 19 MHPUE WIRING DIAGRAMS 1 Phase MHPUE 90 3 Phase MHPUE 90 ...
Page 20: ... 20 3 Phase MHPUE 100 to 130 ...